TheEvolutionofSeismicDesignofFireSprinklerSystems
RussellP.Fleming,P.E.
ExecutiveVicePresident
NationalFireSprinklerAssociation
Patterson,NY
SpecialfiresprinklersysteminstallationguidanceintendedtoguardagainstdamageduetoearthquakesfirstappearedintheNorthAmericansprinklerinstallationstandardin1947,andwaslargelybasedonexperienceintheLongBeachearthquakeof1930.AtthattimemanybuildingcodesinuseintheUnitedStatesdidnotevenaddressthesubjectofearthquakes.InsurancereportsoftheLongBeachearthquakehadindicated90damagedsprinklersystems.Thefirstguidance,containedonlyintheappendix,calledfor1to2inchesclearancearoundpipes,flexiblecouplingsinrisersand“someformoflateralandlongitudinalbracing”forfeedandcrossmains.
Inthe1951editionrequirementswereplacedinthebodyofthestandardforplacementof
longitudinalandlateralbraceswithspacingindicatedas“30to40ft”,amaximum
slendernessratioofbracemembersof200,andflexiblecouplingsonriserswhereitwas
necessarytoprotectsystemsagainstearthquakes.Thestatedintentwastolaterallybrace
for50%ofweightofwater-filledpipingandattachments.
Inthedecadessincethendeliberateeffortshavebeenmadetoclarifytherulesand
improveprotectionwithinthetextofNFPA13–InstallationofSprinklerSystems,but
alwayswiththeintentofaddressing“how”systemsaretobeprotectedagainst
earthquakes,not“where”suchprotectionistobeprovided.Itwasrecognizedthat
buildingcodesandotherauthoritiesmadethebasicdecisionswithregardtothelocation
ofearthquake-proneareas.
AlthoughtheearliestguidancecontainedinNFPA13camefromtheinsuranceindustry
inthewesternstates,theNFPACommitteeonAutomaticSprinklersformedan
EarthquakeProtectionSubcommitteein1985.Oneofthegoalsofthissubcommitteewas
todevelopameanstoaddressthebracingofsprinklersystemsinthesamemannerthat
theapplicationofsystemhydraulicshadbeenaccomplished.Althoughacomplex
subject,itwasbelievedthatmanyofthedesignaspectscouldbepre-engineeredinto
tablesandthenproperlyappliedbythetechnicianswhonormallylayoutanddetailfire
sprinklersystems.The1983standardcontainednoinformationonthesizingorfastening
ofbracingrelativetoloads.Amethodwasproposedin1984whereby“zonesof
influence”couldbeevaluatedtodeterminetotalloadsforproposedbracelocations.
Tableswereproposedfordeterminingmaximumbraceloadsandallowablefastenerloads
basedonsixdifferentcombinationsofbraceandfastenerorientationandanglefrom
vertical.
Thisconceptandtheaccompanyingtableswereacceptedintotheappendixof
thestandardinthe1987edition,andinthe1989editionthetableswereexpandedtonine
combinationsoforientationandangleandmovedintothebodyofthestandard.
2007StructuresCongress:
NewHorizonsandBetterPractices©2007ASCE
CopyrightASCE2007StructuresCongress2007
Downloaded06Mar2009to202.118.74.100.RedistributionsubjecttoASCElicenseorcopyright;seehttp:
//ascelibrary.orgTheNFPA13EarthquakeProtectionSubcommitteewasinplaceatthetimeoftheLoma
PrietaandNorthridgeearthquakesin1989and1994,andheldpublichearingsin
cooperationwiththeNationalFireSprinklerAssociationandtheSocietyofFire
ProtectionEngineersfollowingthoseeventsinordertoevaluatehowfiresprinkler
systemsperformedduringtheearthquakesandstodevelopsuggestionsforimprovements
totheprotectioncriteriawithinthestandard.
Ingeneral,theperformanceoffiresprinklersystemsinthoseearthquakeswasjudgedtobegood,withastrongcorrelationbetweenobservedfailuresanddeparturesfromtherulesofNFPA13.Oneareaacknowledgedtobeinneedofimprovementwastheinteractionofsprinklersandceilings;impactofsprinklersagainstrigidceilingsresultedinaseveralhigh-profileincidentsinwhichanumberofsprinklersopenedandwaterdamageresulted.In1999theNFPAsprinklerprojectwasreorganized.ResponsibilitiesfortheearthquakeprotectionrulesweregiventoanewNFPATechnicalCommitteeonHangingandBracingofWater-BasedFireProtectionSystems,oneoffourseparatetechnicalcommitteescoordinatedthroughaTechnicalCorrelatingCommitteeresponsibleforNFPA13.Thisallowedthedirectinputofmoreearthquakeengineeringexpertiseintothestandarddevelopmentprocess.
Majorchangesinbuildingcoderequirementsforearthquakeprotectionhavetakenplaceinthepasttwentyyears,mainlyduetotheNationalEarthquakeHazardsReductionProgram(NEHRP)provisionsdevelopedwithfundingfromtheFederalEmergencyManagementAgency.TheNEHRPprovisionsinitiallyfoundtheirwayintothecodes
throughdirectadoption,andmorerecentlythroughreferencetotheAmericanSocietyofCivilEngineer’sstandardASCE/SEI7.Asaresult,thegoalofthecommitteethatpreparesNFPA13hasevolvedduringtheyears.Fromtheoriginalgoalofindependentlyprovidingameansofprotectingsprinklersystemsagainstearthquakeforces,thecommitteeinrecentyearshasbeentryingtokeeppacewithamovingtargetassuccessiveeditionsofASCE/SEI7addressprotectionofarchitecturalandmechanicalsystems.
ThereisadifficulttransitionperiodtakingplacerightnowinvolvingtheseismicprovisionsofNFPA13andthe2003editionoftheInternationalBuildingCode®(IBC).BecauseofthereferencetoASCE/SEI7,the2003IBCdoesnotcontainthedetailedseismicrequirementsthathadbeenincludedinthe2000editionoftheIBC.Althoughgeneralreferencetothe1999editionofNFPA13iscontainedinthe2003IBC,asectionofASCE/SEI7thatmadespecialreferencetotheuseofNFPA13forearthquake
protectionwasomittedduringtheadoptionprocess,leadingsometobelievethat
sprinklerpipingmustbeprotectedthesameasothermechanicalpiping.However,
sprinklersystempipingisnotarrangedlikeothermechanicalpipingsystems,andsome
oftherulesofNFPA13havebeenspecificallydevelopedtopreventsystemdamage
duringearthquakemovement.Forexample,whilemostmechanicalpipingsupportedby
hangerrodslessthan12in.(400mm)inlengthisexemptfrombracingundercurrent
codes,comparativeexperienceofsprinklersystemswiththatexemptionversustheNFPA
exemptionofonly6in(150m)wasprovidedbythe1987NewZealandearthquake.The
2007StructuresCongress:
NewHorizonsandBetterPractices©2007ASCE
CopyrightASCE2007StructuresCongress2007
Downloaded06Mar2009to202.118.74.100.RedistributionsubjecttoASCElicenseorcopyright;seehttp:
//ascelibrary.orggeneralconclusionwasthatsystemsinstalledinaccordancewithNFPA13withstoodthe
earthquake,whilethosenotsodesignedfailed.
Overthepasttwodecadestherehavebeenanumerousrefinementsinthelanguageof
NFPA13thatreflectthelessonslearnedinearthquakesaswellastheinfluenceofthe
NEHRPprovisions.Thesecanbeevaluatedbylookingathowthevarioussectionsof
NFPA13haveevolvedintwentykeyareas:
1.ApplicabilityofNFPA13EarthquakeProtectionProvisions
1983-Wheresubjecttoearthquakes
1996-Whensprinklersystems…aretobeprotectedagainstdamagefromearthquakes
1999-Wheresprinklersystemsorabovegroundfireservicemainsarerequiredtobe
protectedagainstdamagefromearthquakes
2002-Wherewater-basedfireprotectionsystemsarerequiredtobeprotectedagainst
damagefromearthquakes
2.GeneralIntentofEarthquakeProtectionProvisions
1983-Minimizeorpreventpipebreakage
1991-Preventpipebreakage
1999-Protectagainstdamage
3.FlexibleCouplings-General
1983-Forpiping3½in.orlarger
1994-Forpiping2½in.orlarger;“Flexiblelistedpipecoupling”definedas“alisted
couplingorfittingthatallowsaxialdisplacement,rotation,andatleast1degree
ofangularmovementofthepipewithoutinducingharmonthepipe”(minimum
0.5degreesfor8-in.andlarger)
2007-Flexiblecouplingsandclearanceidentifiedasaddressingdisplacementdueto
storydrift
4.FlexibleCouplingsforRisersinMulti-StoryBuildings
1983-Atceilingofeachintermediatefloor
1994-Within12in.aboveandbelowthefloorinmultistorybuildingssuchthatthe
flexiblecouplingbelowthefloorisbelowthemainsupplyingthatfloor
2007StructuresCongress:
NewHorizonsandBetterPractices©2007ASCE
CopyrightASCE2007StructuresCongress2007
Downloaded06Mar2009to202.118.74.100.RedistributionsubjecttoASCElicenseorcopyright;seehttp:
//ascelibrary.org
1999-Within12in.aboveandwithin24in.belowthefloorinmultistorybuildings;
Additionalcouplingrequiredonverticalportionoftie-inpipingwheretie-inis
belowtheupperflexiblecouplingontheriser
2007-Additionalflexiblecouplingcanbeprovidedeitherontheverticalportionoftie-in
pipingorwithin24in.onhorizontaltie-inpiping
5.DropstoHoseLines,SprinklersinRacks,andPortionsofSystems
1983-Fittingswithflexiblejointsatthetopofdropstohoselines(regardlessofsize);
Swingjointsassembledwithflexiblefittingsondropstoracksover3in.
1987-Flexiblecouplingsatthetopofdropstohoselines(regardlessofsize);Swing
jointswithflexiblefittingsondropstoracks(regardlessofsize)
1989-Flexiblecouplingatthetopofdropstohoselines,racksprinklersandmezzanines
(regardlessofsize);Flexiblecouplingatthetopofdropsexceeding15ft.to
sprinklersorportionsofsystems(regardlessofsize)
1991-Flexiblecouplingwithin24in.ofthe