SECTION115313
SECTION115313
(FORMERLY11610)
LABORATORYFUMEHOODS
Displayhiddennotestospecifierbyusing"Tools/Options/View/HiddenText”
**NOTETOSPECIFIER**MottManufacturingLtd.;Sigma‘Pro’LaboratoryFumeHoods,Sigma‘Pro’auxiliaryairLaboratoryFumeHoods,PerchloricAcidLaboratoryFumeHoods,RFVLaboratoryFumeHoods,HopecLaboratoryFumeHoods,HydroflouricFumeHoods,ProDemonstrationHoods,FloorMountedHoods.
ThissectionisbasedontheproductsofMottManufacturingLtd.,whichislocatedat:
452HardyRd
Brantford,ONN3T5L8
Tel:
(519)752-7825
Fax:
(519)752-2895
Email:
inquire@mott.ca
www.mott.ca
SECTION115313–LABORATORYFUMEHOODS
PART1–GENERAL
Summary:
ThisSpecificationidentifiestheminimummaterialandconstructionstandardsthatarerequiredtodeliveraqualityinstallationoflaboratoryfumehoods.FumehoodsshallbesuppliedinaccordancewiththerequirementsofthisSpecification.ThefumehoodsidentifiedinthisSpecificationshallincludethemiscellaneousmetalpanelsandotherrelatedcomponentsasidentifiedontheDrawingsandthatarenecessaryforthecompleteinstallation.
Hoodsshallfunctionasventilated,enclosedworkspaces,designedtocapture,confineandexhaustfumes,vapoursandparticulatematterproducedorgeneratedwithintheenclosure.
1.1SECTIONINCLUDES
A.LaboratoryFumeHoods
1.2RELATEDSECTIONS
**NOTETOSPECIFIER**Deletesectionsbelowthatareirrelevanttoproject.Addsectionsasrequired.
A.Division09Section6513,“ResilientBaseandAccessories”
B.Division12Section3600,“Countertops”
C.Division12Section3553,“ManufacturedMetalCasework
D.Division12Section3200,“ManufacturedWoodCasework”
E.Division13Section2100,“ControlledEnvironmentRooms”
F.Division22Section4000,“PlumbingFixtures”
G.Division23Section3000,“HVACAirDistribution”
H.Division26Section0500,“CommonWorkResultsforElectrical”
I.RelatedWorkToBePerformedByOthers:
1.Finalinstallationofallplumbing,serviceandelectricalfixturesattachedtofumehoodorcountertop(excludingpipingandwiringwithinfumehoods).
2.Finalconnectiontoservicelinesofallplumbing,serviceandelectricalfixturesattachedtolaboratorycaseworkorfumehoods.
1.3REFERENCES
**NOTETOSPECIFIER**Deletereferencesbelownotrequiredforproject.
A.SEFA1-2002:
LaboratoryFumeHoods–Design,Materials,UseandTestingGuidelines
ScienceEquipmentandFurnitureAssociation(SEFA)
B.ISO9001:
2000–QualityManagement
InternationalStandardsOrganization(ISO)
C.ADA(ATBCBADAAG)AmericanswithDisabilitiesActAccessibilityGuidelines
AmericanswithDisabilitiesAct(ADA)
1.4SUBMITTALS
RefertoSection013300,“SubmittalProcedures,”forrequirements,procedures,etc.
A.ProductData:
1.Drawingsshallincludedataanddetailsforconstructionofthelaboratoryfumehoodsaswellasinformationregardingthename,quantity,typeandconstructionofmaterials(suchashardware,gauges,etc),thatwillbeusedtocompletetheproject.
B.ShopDrawings:
1.Thelaboratorycaseworkmanufacturershallfurnishshopdrawingsillustratingthelayoutandplacementofalllaboratorycaseworkandfumehoodsaswellasanyproductsincludedinthissection.
2.Indicatethetypeandlocationofallservicefittingsandassociatedsupplyconnections.
3.Preparationinstructionsandrecommendations.
4.Storageandhandlingrequirementsandrecommendations.
5.Installationmethods.
C.SelectionSamples:
**NOTETOSPECIFIER**Deleteselectionsamplesifcolorshavealreadybeenselected.
Submitthefollowing:
1.Onecompletesetofcolorchipsrepresentingthemanufacturer’sfullrangeofavailablecolors.Minimumsamplesize2inchesby3inches(50mmx76mm).
D.QualityAssurance/Control
1.DesignData/TestReports:
Manufacturershallsubmittestdataanddesigncriteriawhichareincompliancewiththeprojectspecifications.
**NOTETOSPECIFIER**Ifauxiliaryairmodelisbeingusedrewordthefirstsentencetostate“FumeHoods,SigmaSystems“Pro”auxiliaryairmodel,”
IfHOPECmodelisbeingusedrewordthefirstsentencetostate“FumeHoods,SigmaSystems“HOPECTYPE”model,”
IftheRFVmodelisbeingusedrewordthefirstsentencetostate“FumeHoods,SigmaSystems“RFV”model,”
2.Performance:
FumeHoods,SigmaSystems“Pro”model,shallbedesignedtomeetorexceedtheAmericanStandardforLaboratoryVentilationandtheAmericanIndustrialHygieneAssociationstandardasdescribedinANSI/AIHAZ9.5.ThisstandardofperformanceshallbeverifiedthroughfactorytestinginaccordancewiththeestablishedprotocolassetoutbytheANSI/ASHRAE110standard.
3.Certificates:
Allcertificationsrequiredinthespecificationsshallbesubmittedwiththeoriginalsubmittalpackageunderseparatecover.Certificatesmustbeprovidedwiththesignatureofaqualifiedindividualofthesupplier.
4.Manufacturers’Instructions:
Providemanufacturer’sinstructionsforinstallationandmaintenanceofallproductsprovidedandinstalledwithinthissection.Instructionswillbeinboundform,tabbedandorganizedbysectionnumber.
5.Submitcopyofthecorrosionresistantlabeltobeattachedtothefumehoodexteriorwithcondensedinformationcoveringrecommendedlocationsforapparatusandaccessories.
1.5QUALITYASSURANCE
A.ManufacturerQualifications:
1.ThefollowinglistofinformationwillbeprovidetotheArchitectatleastten(10)dayspriortothebidopening:
2.Listofmanufacturingfacilities;
3.ManufactureroffumehoodsshallhavethecapabilitywithintheirfacilityofperformingfumehoodtestsbasedonthelatestANSI/ASHRAESpecification110.
4.Alistoften(10)installationsofcomparablestaturecompletedwithinthepast5years;
5.Constructiondetailsdepictingthematerials,sizesandmethodsofconstruction;
B.Mock-Ups
**NOTETOSPECIFIER**Includeamock-upiftheprojectsizeand/orqualitywarranttakingsuchaprecaution.Thefollowingisoneexampleofhowamock-uponalargeprojectmightbespecified.Whendecidingontheextentofthemock-up,considerallthemajordifferenttypesofworkontheproject.
1.Areamockupsshallbeasindicatedontheshopdrawings.Postbidmockupareasmustbepricedfordisassemblyandreassemblyandusedwithintheproject.
2.DonotproceedwithremainingworkuntilinstallationisapprovedbyArchitect.
a)Installbasecabinetwithspecifiedhardware.
b)Installfumehoodwithspecifiedfixtures.
1.6DELIVERY,STORAGEANDHANDLING
A.Packaging,Shipping,HandlingandUnloading
1.Packaging:
Productsshallhavepackagingadequateenoughtoprotectfinishedsurfacesfromsoilingordamageduringshipping,deliveryandinstallation.
2.Delivery:
Fumehooddeliveryshallonlytakeplaceafterpainting,utilityrough-insandrelatedactivitiesarecompletedthatcouldotherwisedamage,soilordeterioratefumehoodsininstallationareas.
3.Handling:
Care,suchastheuseofpropermovingequipment,experiencedmovers,etc.,shallbeusedatalltimestoavoiddamagingthefumehoods.Untilinstallationtakesplace,anywrapping,insulationorothermethodofprotectionappliedtoproductsfromthefactorywillbeleftinplacetoavoidaccidentaldamage.
B.AcceptanceatSite:
1.FumehoodswillnotbedeliveredorinstalleduntiltheconditionsspecifiedunderPart3,Installationsectionofthisdocumenthavebeenmet.
C.Storage:
1.Fumehoodsshallbestoredintheareaofinstallation.If,priortoinstallation,itisnecessaryforthefumehoodstobetemporarilystoredinanareaotherthantheinstallationarea,theenvironmentalconditionsshallmeettheenvironmentalrequirementsspecifiedundertheProjectSiteConditionsarticleofthissection.
D.WasteManagementandDisposal:
1.Thesupplierofthelaboratoryfumehoodsareresponsibleforremovinganywasteorrefuseresultingfromtheinstallationof,orworkpertainingtolaboratoryfumehoods;therebyleavingtheprojectsitecleanandfreeofdebris.Trashcontainer(s)tobeprovidedbyothers.
1.7PROJECTSITECONDITIONS
A.Buildingmustbeenclosed(windowsanddoorssealedandweather-tight);
B.AnoperationalHVACsystemthatmaintainstemperatureandhumidityatoccupancylevelsmustbeinplace;
C.Adjacentandrelatedworkshallbecomplete;
D.Ceiling,overheadductworkandlightingmustbeinstalled;
E.Sitemustbefreeofanyfurtherconstructionsuchas“wetwork”;
F.Requiredcaseworkmustbeinstalledaccuratelyandtheprojectmustbereadyforfumehoodinstallation.
1.8WARRANTY
A.FurnishawrittenwarrantythatWorkperformedunderthisSectionshallremainfreefromdefectsastomaterialsandworkmanshipforaperiodoftwo
(2)yearsfromdateofshipment.DefectsinmaterialsandworkmanshipthatmaydevelopwithinthistimearetobereplacedwithoutcostorexpensetotheOwner.
Defectsinclude,butarenotlimitedto:
1.Ruptured,cracked,orstainedcoating
2.Discolorationorlackoffinishintegrity
3.Crackingorpeelingoffinish
4.Slippage,shift,orfailureofattachmenttowall,floor,orceiling
5.Weldorstructuralfailure
6.Warpingorunloadeddeflectionofcomponents
7.Failureofhardware
B.ThewarrantywithrespecttoproductsofanothermanufacturersoldbyMottManufacturingislimitedtothewarrantyextendedbythatmanufacturertoMottManufacturing.
PART2–PRODUCTS
2.1MANUFACTURER
**NOTETOSPECIFIER**DeleteormodifythefollowingparagraphstocoordinatewiththeOwner’srequirements.
A.AcceptableManufacturer:
MottManufacturingLtd.;452HardyRd.Brantford,ON,CanadaN3T5L8.Tel:
(519)752-7825.Fax:
(519)752-2895.Email:
in