GCS5200BusWiring08
GCS5200
Version1.0:
August,2008
BUS-WIRING
GeneralElectricityCompanyofLibya
TABLEOFCONTENTS
1.Scope1
2.Flowchart1
3.Constructionmethod2
3.1ClassificationsofBus(RefertoGDS5200“bus-barscheme”)2
3.2SelectionofBus-barScheme3
3.2.1bus-barschemes3
3.3Singlelinediagramsforbus-barscheme3
3.3.1Primaryside3
3.3.2Secondaryside4
3.4DrawingofInsulatorStringSet(RefertoGDS6400AppendixC)6
3.4.166kVsinglesuspensionset6
3.4.266kVsingletensionset7
4.Workingprocedure8
5.Checklist16
LISTOFFIGURES
1.Scope
Thisstandardisapplicabletoinstallationofbus-barforthenew66kV,30kVsubstations.
2.Flowchart
3.Constructionmethod
Busesinthesubstationaremajorfacilitiesthosearetakeninchargeofthegatheringanddistributingofthecurrentflow,also,whichwillplayamajorroleintheelectricpowertrade.Busfaultslittlehappeninthepowersystem,ifany,itdecreasereliabilityandstabilityforoverallpowersystem.Themaincausesarenaturalinsulationaging,lightingandmistakenoperation.
3.1ClassificationsofBus(RefertoGDS5200“bus-barscheme”)
Classificationsofbusinsubstationsareclassifiedasmainbus,branchbusandoutgoingbusandtheserolesareasfollows;
▪Mainbus
Themainbusshallmanagethecurrentflowofallfeeders.Therefore,thistermmeansthatallfeedersareconnectedtomainbussuchasdivergencebuses,outgoingbusestomakeintegratedcurrentflowsasshowninfigurebelow
▪Branchbus
Indoublebus-barscheme,thebranchbusshallbeconnectedbetweenmainbusesasshowninfigurebelow
▪Outgoingbus
Outgoingbusshallconnectedtothemainbusorbranchbustoconnectthefeederlinesorthetransformerlinesasshowninfigurebelow
3.2SelectionofBus-barScheme
3.2.1bus-barschemes
Busvoltage
Substation
66kV
30kV
11kV
Remark
66kV
2B-1CB
1B-1CB
-
2B-1CB
1B-1CB
30kV
-
2B-1CB
2B-1CB
1B-1CB
Note:
1.B:
Numbersofbus(2B:
Doublebus,1B:
Singlebus)
2.CB:
Numbersofcircuitbreakerperacircuit
3.3Singlelinediagramsforbus-barscheme
3.3.1Primaryside
Note:
1)Ifthebussectionbreakerisnecessary,thebussectionCBshallbeinstalledwiththebussectionDS
2)TheBustiebreakersshouldbeinstalledforbusprotectionwheneveritwasdividedbythebussection
Note:
ThewithdrawaltypeCBshallbeapplicabletothiscasetoreducetherequiredareaaccordingtothemanufacturer’sspecification
3.3.2Secondaryside
a)Doublebusandsinglebreaker
Theareaswhicharerequiredthehighlyreliablesupplyorexpectedthehugedamagewhenamomentaryoutageoccursinanelectricitysupplysuchasthemajornationalandpublicfacilities,hospitals,sewagetreatmentplantsandsoforth
Note:
1)Bussectionbreakersshallbeinstalledwheneverpowertransformersareinstalled
2)Consideringthesmoothbuschanging,thebustieCBshallbeinstalledasshowingabove
b)Singlebusandsinglebreaker
Theareaswhicharelocatedinaruralareaandrequiredthelowloaddemands,alsonotexpectedtheloadincreaseinthefuture
Note:
Bussectionbreakersshallbeinstalledwhenevertransformersareinstalled
3.4DrawingofInsulatorStringSet(RefertoGDS6400AppendixC)
3.4.166kVsinglesuspensionset
Item
Denomination
N
GESCode
M.B.S
1
Anchorshackle
1
1202040
120KN
2
Balleye
1
1202145
120KN
3
Arcinghorn
2
1242310
4
Sockettongue
1
1242245
120KN
5
Suspensionclamp
1
124306*
120KN
6
Insulators
U100BLP
3.4.266kVsingletensionset
Item
Denomination
N
GESCode
M.B.S
1
Anchorshackle
1
1202050
160KN
2
Balleye
1
1202155
160KN
3
Arcinghorn
2
1242330
4
Sockettongue
1
1242255
160KN
5
Compressiondeadclamp
1
12431**
95%cond
6
Insulators
U160BL
4.Workingprocedure
4.1Acceptance,storageandpreparation
4.2Hardwareinstallation
4.3Insulatorinstallation
4.4Buswiring
4.5Branchlineconnection
Procedure
Figures
1.Acceptance
(a)Checkquantityandspecificationofhardware,insulatorandwire.
(b)Checkpackingconditionforinsulatorandwire
(c)Checkdeformationanddamageofthematerials.
2.Storage
(a)Materialsshouldbeassortedbyitemandspecificationandloadedonthesplint
(b)Hardwareshouldbenotcorrodedandtarnished
(c)Insulatorandwirearecarriedinaconditionofpacking
(d)Itrequirescarenottodamagetheirsurfacewhenhardwareandwirearecarriedandkept,becausetheirsurfacehaveanimportanteffectonyieldofcorona
3.Preparation
Checkquantityofinsulatorsandhardwareaswellasinsulatorinstallationplanforbuswiring.
(a)Checkwhetherhardwarestandardandquantityaresuitable.
(b)Priortobuswiring,examinebuswiringmethodthoroughly.
(c)Inspectcompressiontool,wiringequipmentandtools.
Procedure
Figures
1.Strainandsuspensionclampinstallation
(a)Assembleboltsandnutsintohardwareontheground.Andcheckit.
(b)Beforeusinghardware,cleanthehardwareandcheckitscrackordeformation.
(c)AdjustwiresupportinghardwarepositionunderU-bolt.
(d)TightenallU-boltequally.
2.PGClampInstallation
(a)Assembleboltsandnutsintohardwareontheground.Andcheckit.
(b)Beforeusinghardware,cleanthehardwareandcheckitscrackordeformation
(c)Cleanwireconnectedareawithmetalbrushorsandpapertoremoveimpuritiesandoxide.
(d)Tightenallboltsequally.
3.CompressivedeadendclampInstallation
3.1Inspectionforconnectiontool
(a)Checkthecompressorperformanceandoilpressuregaugeaccuracy.
(b)Checkdiessizeandabrasionduringtotalconstructionprocedure.
3.2Cuttingwire
(a)Checkcompressivedeadendclampsize.
(b)Determinecuttingpositionbyexaminingthatwireisdamaged,bentandswollen.
(c)Windabinderwireaboutthreetimes3cminsidethecuttingpoint.
(d)Markthecuttingpointusingamputator.
(e)WhenusingAlcuttertocuttheAlwire,becarefulthattheedgeofwireisnotdamaged.CuthalfthelastlayerofAlwirewithcutters.Theremaininghalfshouldbecutbyhandtopreventcuttersfromdamagingthesteelcore.
(f)ExposethesteelcoreaftercuttingAlwireattheendofwire.
(g)Windbinderwirearoundexposedsteelcore.
3.3Cleaningthewire
(a)CleanAlwiresurfacebyrubbingitwithawirebrush.
A.Ifnecessary,removetherustforsteelcore.
B.IfAlwiresareoldenough,untwistandcleaneachAlwirethoroughly.
(b)CleanupinsideAlsleevewithbenzene.
3.4Dead-endclampCompression
(a)Aftercleaningwiresurfacewithwirebrush,insertAlclampintowireconsideringrightinsertdirection.
(b)Afterassemblingclampwithcompressiondies,insertsteelcoretightly.
(c)Whilekeepingwireeven,compressthedieswithbeingpileduponeonanotherbyonethirdfrominsideclamptowire.
(d)Aftercompressionwork,removeforeignsubstances.Checktheresultbycompressiongaugeandtakepicturesinordertorecordresults.
(e)Compressionworkcautionsareasfollows;
A.IfSteelcorebecomestwistedaftercompression,Alclampcouldnotbeinserted.SokeeptheSteelcoreeventomakeSteelclampstraightwhencompressingit.
B.AlthoughcorrodedSteelclampiscompressedwithsteelcore,steelcoreandsteelclamparestillseparated.SodonotusecorrodedSteelclamp.
(f)PutAlclamponcompressedsteelcore.FillitwithconductivecompoundthroughthecompoundinletasmuchascompoundflowoutAlsleeveduringcompressionwork.
(g)Compressthecompresseddieswithbeingpileduponeonanotherbyonethirdtowardtransmissionlinealongcompressiondirectionline.
(h)Afterremovingforeignsubstancesaroundcompressedarea,checktheresultbycompressiongaugeandtakepicturestorecordtheresult.
(i)Aftercompression,anamountofcompoundmustcomeoutequallyfromAlSleevearound.Andbirdcagingmustbeeliminated.
Procedure
Figures
1.Thestandardinsulatorquantity
Thenumberofinsulatorconnectedtoperinsulatorstringshallbeusedaccordingto
Kind
Pollutionlevel
Light
Medium
Heavy
Veryheavy
Suspensionstringset
6
6
6
6
Tensionstringset
5
5
6
7
4.2Insulatorsupportingset
Adoptstringsetforinsulatorsupportingdeviceofstrainbus.
4.3InsulatorStringInstallation
(a)Makesurethatallinsulatorsaredryandcleanbeforeusingthem.Checkinsulationresistanceanduseonlyqualifiedinsulators.
A.Useins