BlastFurnaceFinesReturnTransmittingSystem
IncludingdevicesMix.405,Mix.406.
Mix.406:
beltconveyor(FC-1)
Mix.405:
beltconveyor(FC-2)
Alldevicesarestopped,thenPLCfinishthesystemstopprocess
Alldevicesarerunning,thenPLCfinishthesystemstartprocess.Insystemstartprocess,ifthereisanydevicemultiplefault,PLCfinishthesystemstartprocess,SCADAshowalarmmessageandPLCiswaitingnextcommand.
Alldevicesinremotecondition,systeminremotecondition.
Alldevices’selectricloopareready,systemisready.
Thereisnotanymultiplefault,systemishealthy
Whenallabovethreeconditionsareok,systemisok,theinterlockstart/stopcommandbuttonispermitted,InSCADA.
1.electricsymbol:
Mix.405technologysymbol:
FC-1
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorDorEorForG)
A.deviceoverload
B.swayswitchfault
C.pullcordfault
D.afterstartthedevice,ifnorunningstatussignalfeedback
E.inSCADAoperatorclickemergencybutton
F.deviceisrunning,butrunningstatussignallost
G.afterdevicekeeprunning10s,PLCreceivezerospeedsensorfaultsignal
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
(AandB)
A.Alldevicesareok
B.FC-2beltconveyorisrunning
(4).deviceinterlockemergencystopconditions
(AorB)
A.FC-2beltconveyorisstopped
B.FC-1beltconveyormultiplefaultcoming
(5).deviceinterlockstopconditions
A.FC-2beltconveyorisstopped
2.electricsymbol:
Mix.406technologysymbol:
FC-2
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorDorEorForG)
A.deviceoverload
B.swayswitchfault
C.pullcordfault
D.afterstartthedevice,ifnorunningstatussignalfeedback
E.inSCADAoperatorclickemergencybutton
F.deviceisrunning,butrunningstatussignallost
G.afterdevicekeeprunning10s,PLCreceivezerospeedsensorfaultsignal
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
A.Alldevicesareok
(4).deviceinterlockemergencystopconditions
A.FC-1beltconveyormultiplefaultsignalcoming
(5).deviceinterlockemergencystopconditions
A.Alwayspermitted
3.blastfurnacefinesreturntransmittingsysteminterlockdescribe
(1).blastfurnacefinesreturntransmittingsysteminterlockstartconditions
(AandBandCandD)
A.alldeviceinremotecontrolcondition
B.alldeviceinremotecontrolconditionelectricloopisready
C.alldevicenotanyonemultiplefaultsignal
D.inSCADA,operatorswitchFCsystemtoautomode
(2).blastfurnacefinesreturntransmittingsysteminterlockstartsequence
FC-2→FC-1
(3).blastfurnacefinesreturntransmittingsysteminterlockstopsequence
FC-1→FC-2
4.blastfurnacefinesreturntransmittingsystemstartflow
SequenceStart
No
Alldevicesareok?
YESt=5s
FC-2Start
No
FC-1Fault
FC-2isRunning?
YESt=5s
FC-1Start
No
FC-2Fault
FC-2isRunning?
YES
ResetStartCommand
End
5.blastfurnacefinesreturntransmittingsystemstopflow
SequenceStop
No
AlldevicesareRemote?
Yes
Yes
AlldevicesareStopped?
NOt=5s
FC-1Stop
No
FC-1isstopped?
Waiting
YESt=5s
FC-2Stop
No
FC-2isStopped?
Waiting
YES
ResetStopCommand
End
MaterialTransmittingSystem
Includingdevices:
Pro.SL01,Pro.SL02.
Pro.SL01:
beltconveyor(RM-1)
Pro.SL02:
beltconveyor(RM-2)
Alldevicesarestopped,thenPLCfinishthesystemstopprocess
Alldevicesarerunning,thenPLCfinishthesystemstartprocess.Insystemstartprocess,ifthereisanydevicemultiplefault,PLCfinishthesystemstartprocess,SCADAshowalarmmessageandPLCiswaitingnextcommand.
Alldevicesinremotecondition,systeminremotecondition.
Alldevices’selectricloopareready,systemisready.
Thereisnotanymultiplefault,systemishealthy
Whenallabovethreeconditionsareok,systemisok,theinterlockstart/stopcommandbuttonispermitted,InSCADA.
1.electricsymbol:
Pro.SL01technologysymbol:
RM-1
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorDorEorForG)
A.deviceoverload
B.swayswitchfault
C.pullcordfault
D.afterstartthedevice,ifnorunningstatussignalfeedback
E.inSCADAoperatorclickemergencybutton
F.deviceisrunning,butrunningstatussignallost
G.afterdevicekeeprunning10s,PLCreceivezerospeedsensorfaultsignal
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
(AorB)
A.Alldeviceareok
B.SL02beltconveyorisrunning
(4).deviceinterlockemergencystopconditions
(AorB)
A.SL02beltconveyorisstopped
B.SL01beltconveyormultiplefaultcoming
(5).deviceinterlockstopconditions
A.SL02beltconveyorisstopped
2.electricsymbol:
Pro.SL02technologysymbol:
SL02
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorDorEorForG)
A.deviceoverload
B.swayswitchfault
C.pullcordfault
D.afterstartthedevice,ifnorunningstatussignalfeedback
E.inSCADAoperatorclickemergencybutton
F.deviceisrunning,butrunningstatussignallost
G.afterdevicekeeprunning10s,PLCreceivezerospeedsensorfaultsignal
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
A.Alldevicesareok
(4).deviceinterlockstopconditions
A.RM-2beltconveyormultiplefaultsignalcoming
(5).deviceinterlockemergencystopconditions
A.Alwayspermitted
3.MaterialTransmittingSystem
(1).Materialtransmittingsysteminterlockstartconditions
(AandBandCandD)
A.alldeviceinremotecontrolcondition
B.alldeviceinremotecontrolconditionelectricloopisready
C.alldevicenotanyonemultiplefaultsignal
D.inSCADA,operatorswitchMTsystemtoautomode
(2).Materialtransmittingsysteminterlockstartsequence
SL02→SL01
(3).Materialtransmittingsysteminterlockstopsequence
SL01→SL02
4.MaterialTransmittingsystemstartflow
SequenceStart
No
Alldevicesareok?
YESt=5s
RM-2Start
No
RM-1Fault
RM-2isRunning?
YESt=5s
RM-1Start
No
RM-2Fault
RM-2isRunning?
YES
ResetStartCommand
End
5.MaterialTransmittingsystemstopflow
SequenceStop
No
AlldevicesareRemote?
Yes
Yes
AlldevicesareStopped?
NOt=5s
RM-1Stop
No
RM-1isstopped?
Waiting
YESt=5s
RM-2Stop
No
RM-2isStopped?
Waiting
YES
ResetStopCommand
End
CokeTransmitSystem
Includingdevices:
Pro.R01,Pro.R02,Pro.R03,Pro.R04,Pro.R05,Pro.R06,Pro.MC1
Pro.R01:
VibratorFeeder(VF-1)
Pro.R02:
beltconveyor(F-2)
Pro.R03:
FourRollersCrasher(CRC-1)
Pro.R04:
beltconveyor(F-2)
Pro.R05:
beltconveyor(F-3)
Pro.R06:
beltconveyor(F-4)
Pro.MC1:
MagneticSeparatoronlylocalcontrolmode(MS-1)
InthisSystem“Alldevice”excludingMS-1,Magneticseparatoronlylocalcontrolmode
Alldevicesarestopped,thenPLCfinishthesystemstopprocess
Alldevicesarerunning,thenPLCfinishthesystemstartprocess.Insystemstartprocess,ifthereisanydevicemultiplefault,PLCfinishthesystemstartprocess,SCADAshowalarmmessageandPLCiswaitingnextcommand.
Alldevicesinremotecondition,systeminremotecondition.
Alldevices’selectricloopareready,systemisready.
Thereisnotanymultiplefault,systemishealthy
Whenallabovethreeconditionsareok,systemisok,theinterlockstart/stopcommandbuttonispermitted,InSCADA.
1.electricsymbol:
Pro.R01technologysymbol:
VF-1
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorD)
A.deviceoverload
B.afterstartthedevice,ifnorunningstatussignalfeedback
C.inSCADAoperatorclickemergencybutton
D.deviceisrunning,butrunningstatussignallost
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
(AandB)
A.Alldevicesareok
B.F-1beltconveyorisrunning
(4).deviceinterlockemergencystopconditions
(AorB)
A.F-1beltconveyorisstopped
B.VF-1beltconveyormultiplefaultcoming
(5).deviceinterlockstopconditions
A.F-1beltconveyorisstopped
2.electricsymbol:
Pro.R02technologysymbol:
F-1
(1).anyoneoftheunderconditionsPLCoutputmultiplefault
(AorBorCorDorEorForG)
A.deviceoverload
B.swayswitchfault
C.pullcordfault
D.afterstartthedevice,ifnorunningstatussignalfeedback
E.inSCADAoperatorclickemergencybutton
F.deviceisrunning,butrunningstatussignallost
G.afterdevicekeeprunning10s,PLCreceivezerospeedsensorfaultsignal
(2).devicemanualstart/stopconditions
(AandBandCandD)
A.deviceinremotecontrolcondition
B.deviceelectricloopisready
C.devicenomultiplefault
D.inSCADA,operatorselectmanualmode
(3).deviceinterlockstartconditions
(AandBandC)
A.Alldevicesareok
B.CRC-1fourrollerscrash