GW22A252Ⅲ隔离开关说明书E.docx
- 文档编号:29225069
- 上传时间:2023-07-21
- 格式:DOCX
- 页数:34
- 大小:452.16KB
GW22A252Ⅲ隔离开关说明书E.docx
《GW22A252Ⅲ隔离开关说明书E.docx》由会员分享,可在线阅读,更多相关《GW22A252Ⅲ隔离开关说明书E.docx(34页珍藏版)》请在冰豆网上搜索。
GW22A252Ⅲ隔离开关说明书E
GW22A-252Ⅲ型隔离开关
GW22A-252ⅢDISCONNECTORSWITCH
安装维修使用说明书
INSTALLATIONANDOPERATIONMANUAL
编号:
0TK.466.5028
No:
0TK.466.5028
山东泰开隔离开关有限公司
ShandongTaikaiDisconnectorCo.,Ltd
二○一○年五月
May.2010
Catalogue
1、Summary………………………………………………………..…………2
2、Workingconditions…………………………………………..……2
3、Characteristic………………………………………………………..……3
4、Productclarificationsandtechnicalparameters……………………..…4
5、Productstructureandoperationprinciple…………………………..…5
6、Packageandshipping……………………………………………..…8
7、Inspectionandstorage…………………………………………..…8
8、Unloadingandhoisting……………………………………………..…9
9、Installationandcommission…………………………………..…9
10、Acceptanceandfine-tuningbeforeinstallationonsite…………………13
11、Accompanyingdocument………………………………………14
12、Orderingnotice…………………………………………………14
1、Summary…………………………………………………………………………
General
1.Functions
GW22A-252D(W)Ⅲseriesisathree-phase,AC,HVdisconnectorofsinglepost,verticalbreak,singlearmshrinkableclampstyle.(briefedas“GW22A-252Ⅱdisconnector”)isusedinpowersupplysystemwithratedfrequency50Hzandratedvoltage252kV,providingHVlinetotransitionundernoloadconditionsaswellasdisconnectingtherepairedHVbusbar、circuitbreakerandotherhighvoltageelectricequipmentandbetweenliveHVlines.Meanwhile,whentheoperationmodeshouldbealteredinpowergridsystem,itisavailableforbreaking/makingbustransfercurrent,regulatedchargingcurrentofvoltagetransformer,lightningarrestorandect,withoutbreakingormakingon-loadcurrent.
2.Specification
GW22A-252D(W)Ⅲ/J3150-50
Ratedshort-timewithstandcurrent50kA
Ratedcurrent3150A
Motoroperationmechanism
ImproveddesignNo.
Anti-pollution
Withearthingswitch
Ratedvoltage252kV
designNo.22A
Outdoor
隔离Disconnector
3.Standard
◆IEC62271-102HVACDisconnectingSwitchandEarthingSwitch
◆GB/T11022-1999CommonTechnicalRequirementsforHVSwitchgearandControlGear
◆DL/T486-2000OrderingTechnicalConditionsforHVACDisconnectorandEarthingSwitch
◆DL/T593-2006HVACDisconnectorandEarthingSwitch
II、WorkingConditions
◆Ambienttemperature:
-50℃~+50℃;
◆Altitude:
within2000m
◆Windvelocity:
within700Pa
◆Seismicintensity:
9degree;
◆Thicknessoficecovering:
within20mm
◆Pollutionlevel:
class,III,IV
◆Themountingplaceshouldbefarfrominflammable,explosive,corrosivedangerandviolentvibration.
◆Specialworkingconditionsshallbesolvedbyclientsandmanufacturer.
III、Characteristics………………………………………………………………
GW22A-252ⅢdisconnectorisakindofperfectedandimproveddisconnectordevelopedonthebasisofGW22A-252.Itimprovesgoodabilityinfractureofporcelaininsulator、failureofoperationanddistortion、overheatofconductioncircuitaswellasrustcomparingwithotherkindofdisconnectors.Itfocusesonimprovingqualityandoperationreliabilityofequipmentandprovidingthefollowingcharacteristics:
a.Themaincircuitadoptstop-gradeanti-rustal-alloythatprovidesexcellentconductingcapacity,lightweight,highmechanicalintensity;thedrivingpartofthemainblade,balancespring,clampingspring,resetspringaredesignedintheconductpipetofreefromtheeffectbyoutsideenvironment.
b.Flexibleconnectionadoptingpurealuminummaterialwithconductinginterfacesilveredisofgoodconductivityandhighthrough-currentcapacity.Eachaluminumlayerinterfaceisanodizedthatstrengthenanticorrosionperformance.
c.Eachpartofconductingloopexceptdynamicandfixedcontactsmeshingpointsurveyisconnectedandconductcurrentbyfixedflexibleconnection,andsealgumisappliedallaroundfixedconductinginterfaceincaseofmoisture.Thecontacttubesurfaceofstylusandfixedcontactsissilver-coated,dynamicandfixedcontactspressureisenlarged.Suchmeasuresasaddinginsulationsonupperconductingrod(incaseofcurrentflowdivided)istakentoensurereliablethrough-flowofconductingloopwithoutoverheat.
d.Toppressuretrippingdeviceisimprovedtoensurereliablemakingandkeepgoodworkingstateundertheactionofwindforceandelectricdynamicforce.Modifytheinsulatingrollerintostainlessrollertoavoidagingandfragment.
e.Fingerandclampingspringisarrangedoutsideofconductingtubefortheconvenienceofadjuston-siteclampingforceandreplacefaultedfinger.Silasticsealcoveranddirect-actingsealingstructureofoilsealandsmoothshaftisadoptedonbothsideofconductingrodtototallypreventtopenetrationofrainanddustsothatavoidingrustingandfreezingofaccessories.
f.Rockinglinksadoptself-lubricatingbearingandinsulatingoil-freebearing,transmissionlinksadoptshotgalvanizingoscillatingbearing.Allshaftpinmadeupwithaluminumbronzeorstainlessmaterialisofexcellentanticorrosionperformance,smallrotationresistance,smallfitclearance,reliabletransmissiontoavoidspindleseizedbycorrosion.
g.Suchmeasuresasadoptinghigh-qualityrawmaterialsurfaceanti-corrosiontreatmentaretakentoimproveanti-corrosionperformanceofwholeproduct.Forexample,thesurfaceofallsteelaccessoriesishotdipgalvanizedoradoptsstainlessmaterial;allshaftpinusealuminumbronzeorstainlessmaterial;non-conductinginterfaceofconductingtubisanodized.
h.Earthbladeadoptsall-in-one-takestructureofcounterweightbyheavypunch.Earthingdynamiccontactsadoptself-operatedstructurewithsimpleandbeautifulstructure,smalloperationforcehandreliableaction.
i.Theverticaltransmissionrodofmainearthmechanismconnectedtobodywithconnectiontypeofsplintandbeamclamp.Onesideoflevel3driverodinmainearthbladeadoptsUtypeboltandbeamclampconnectionstylewhiletheotheradoptsadjustablejointoftwo-threadworm,cancellingon-siteweldingconvenientlyfortheon-siteinstallation,adjustment,disassembleandmaintenance.
j.ThemainbladeisincorporatedwithCJ6improvedmotormechanism,theearthbladeismatchedwithCSGimprovedhandmechanism,whichprovidesbeautifuloutline,stronganti-corrosivecapacity,excellentwaterproofanddustproofperformances.Thesecondarycomponentsareboughtfromfamousfactories.Interlockfunctionsareavailable.
k.Top-gradepostinsulatorisadopted,themeshingplaceisofwater-proofstructure,whichconformstosafetyfactorofmorethan2.5timesofmechanicalload.
l.Steel-madehot-dippedfoundationsupport,andverticalandhorizontaldrivingrodsareavailablefortheusertoselect.
IV、Productclarificationsandtechnicalparameters……………………………
1.Clarifications
◆Dividedbycurrentrating:
2000A、3150A、5000A;
◆Dividedbyquantityandpositionofearthingswitches:
unearth、earthing;
◆Dividedbydistributionofswithes:
45°arranged、135°arranged、one-linearraged。
2.Maintechnicalparametersseenintable1
Table1
No.
Item
Unit
Technicalparameter
1
Ratedvoltage
kV
252
2
Ratedcurrent
A
2000
3150
5000
3
Disconnector
Ratedpeakwithstandcurrent
kA
125
160
Ratedshort-timewithstandcurrentandduration
kA
50/3
63/3
4
Earthingswitch
Ratedpeakwithstandcurrent
kA
125
Ratedshort-timewithstandcurrentandduration
kA
50/3
5
Rated1minpowerfrequencywithstandvoltage
(effectivevalue)
Toearth
kV
460
Acrosscontact
460+145
6
Ratedlighteningimpulsewithstandvoltage
(peak)
Toearth
kV
1050
Acrosscontact
1050+200
7
Breakbus-transferinductioncurrentcapacity(busbartransfervoltage300V)
A
2520
8
Breaking-makingsmallcapacitivecurrent
A
2
9
Breaking-makingsmallinductivecurrent
A
1
10
Radiointerferencelevel
μV
≤500
11
mechanicallife
time
3000
12
Ratedterminalstaticmechanicalload
Horizontallongitudinal
N
2000
Horizontallateral
1500
Verticalforce
1250
13
Ratedcontactregion(flexiblebusbar/rigidbusbar)
Longitudinaldisplace
mm
200/150
Horizontaltotaldisplace
500/150
Verticaldisplace
250/150
3.Productstructureandparametersseenintable2
Table2
No.
Item
Unit
1
Contactinsulatingdistance(≥mm)
2550
2
Insulatingdistancetoearth(≥mm)
2000
3
Impedanceofmaincircuit(≤μΩ)
≤180
≤150
≤100
4
Threephasedclosingnonsynchronismofmainblade(≤mm)
20
5
Threephasedclosingnonsynchronismofearthingblade(≤mm)
20
6
Opening-closingtimeofmotor-operatingmechanismformainblade(s)
12±1
7
Outputangleofmotor-operatingmechanismformainblade
135°
8
Outputangleofmanpowermechanismforearthingblade
90°
V、Productstructureandoperationprinciple……………………………………
1.Structureofdisconnector
GW22A-252Ⅲdisconnector(single-poleassemblysketchisshowninpic7,three-poleassemblysketchisshowninpic8)mainlyconsistsofpedestal、postinsulator、rotatinginsulator、mainblade、fixedcontact、operatingmechanismetc.Earthswitchcouldbeincorporated.
Thepedestaliscomposedofthechannelsteelandsteelsheet.Thelowerpartisdesignedwithinstallationholetofixwiththefoundation,theupperpartismountedwithinsulationpost,thesideisabletobeinstalledwithearthswitch;anditcouldalsobeinstalledwithmechanicalinterlockplateetc.
Theinsulator,dividingintothepostinsulatorandtherotatinginsulator,ismadebythetop-gradeporcelain.Itestablishestheinsulationtoearthforthelivesystemandguaranteesthemechanicalstabilityforthedisconnectorundermovingorfixedload.
Themainblade,withsinglecantileverandshrinkablestructure,iscomposedbytheupper-pipeequipment、lower-pipeequipment、pedestaletc.Themovingcontactisequippedonthetopofupper-pipeequipmentandthecontactingpressureisproduced