Z084003240SPC017 Insulation Rev 1.docx
- 文档编号:27247222
- 上传时间:2023-06-28
- 格式:DOCX
- 页数:41
- 大小:47.40KB
Z084003240SPC017 Insulation Rev 1.docx
《Z084003240SPC017 Insulation Rev 1.docx》由会员分享,可在线阅读,更多相关《Z084003240SPC017 Insulation Rev 1.docx(41页珍藏版)》请在冰豆网上搜索。
Z084003240SPC017InsulationRev1
KOREANATIONALOILCORPORATION
BLACKGOLDOILSANDSPROJECT
IMVPROJECTNO.Z08400
MECHANICALSPECIFICATIONFORINSULATION
1
26/06/08
IssuedforDesign
M.Paugh
J.Gonzalez
0
05/05/08
IssuedforEngineering
M.Paugh
J.Gonzalez
REV.
NO
DATE
REVISIONDESCRIPTION
ORIGINATOR
CHECKED
APPROVED
TABLEOFCONTENTS
1.0GENERAL3
2.0CODES,REGULATIONS&STANDARDS4
3.0DEFINITIONSOFINSULATION5
4.0MATERIALS5
5.0DESIGN9
6.0INSTALLATION10
7.0INSULATIONMATERIALSELECTION20
8.0INSPECTIONANDTESTING20
9.0HANDLING21
10.0UNITSOFMEASUREMENT21
11.0TABLE1AHOTSERVICEPROCESSINSULATION22
12.0TABLE1BHOTSERVICEPROCESSINSULATION23
13.0TABLE1CHOTSERVICEPROCESSINSULATION24
14.0TABLE1DHOTSERVICEPROCESSINSULATION25
15.0TABLE2PERSONNELPROTECTIONINSULATION26
16.0TABLE3COLDSERVICEINSULATION27
17.0TABLE4CONDENSATIONCONTROLINSULATION28
1.0general
1.1Scope
Thisspecificationshallapplytothematerialsandinstallationofinsulationonpiping,heatexchangers,tanks,vesselsandotherequipment.
1.1.1Thisspecificationshallcoverinsulationfor:
∙HeatandColdConservationandTemperatureMaintenance
∙PreventionofCondensation
∙PersonnelProtection(surfacetemperatureis65°Candover)
1.1.2Thisspecificationdoesnotcoverthefollowinglightindustrialandcommercialapplications:
∙HVACRefrigerationpipingandductwork.
∙Thermalinsulationinbuildingwallsandroofs.
∙Fireproofingandrefractoryapplicationswherefireresistantqualitiesarerequired.
1.1.3TheInsulationManufacturer'sinstructionsandrecommendationsastothemethodofapplication,etc.,shallsupplementthisspecification.
1.2DefinitionofTerms
1.2.1Theword"Contractor"whenusedinthisStandardshallmeanthepartyidentifiedintheContractAgreement.IftheAgreementisaPurchaseOrder,thenContractorshallalsobeindicatetoasSeller.
1.2.2Theword"Owner"whenusedinthisspecificationshallmeanKoreaNationalOilCorporation(KNOC).IftheAgreementisaPurchaseOrder,thenOwnershallalsobereferredtoasBuyer.
1.3Conflictingrequirements
1.3.1InthecaseofconflictbetweenthisspecificationandotherdocumentsintheContractorPurchaseOrder,unlessspecificallystatedbytheorderasanexception,theSellershallnotifyOwnerinwritingandobtainawrittenrulingfromtheOwnerbeforeproceedingwiththeworkaffected.WhereCity,County,ProvincialorFederalcodesconflictwiththisspecification,themorerigidspecificationshallgovern.
2.0CODES,REGULATIONS&STANDARDS
Contractorshallmeetorexceedtherequirementsofthelatesteditionofthefollowingcodes,regulationsandstandards,exceptassupersededherein.Incaseswheremorethanonecode,regulationorstandardapplytothesamecondition,themoststringentshallbefollowed.
2.1IndustryStandardsandCodes
ASTMStandards(AmericanSocietyforTestingandMaterials)
∙A167StainlessandHeatResistingChromiumNickelSteelPlate,SheetandStrip
∙B209AluminumandAluminumAlloySheetandPlate
∙C168StandardDefinitionofTermsRelatingtoThermalInsulatingMaterials
∙C195StandardSpecificationforMineralFiberThermalInsulatingCement
∙C449MineralFiberHydraulic-SettingInsulatingandFinishingCement
∙C533CalciumSilicateBlockandPipeThermalInsulation
∙C534PreformedFlexibleElastomericThermalInsulationinSheetandTubularForm
∙C547MineralFiberPreformedPipeInsulation
∙C552CellularGlassBlockandPipeThermalInsulation
∙C585PracticeforInnerandOuterDiametersofRigidThermalInsulationforNominalSizesofPipeandTubing(NPSSystem)
∙C591SpecificationforUn-facedPreformedRigidCellularPolyurethaneThermalInsulation
∙C592MineralFiberBlanketInsulationandBlanketTypePipeInsulation(MetalMeshCovered)(IndustrialType)
∙C610ExpandedPerliteBlockandPipeThermalInsulation
∙C612MineralFiberBlockandBoardThermalInsulation
∙C647StandardGuidetoPropertiesandTestsofMasticsandCoatingFinishesforThermalInsulation
∙C795InsulationforUseoverAusteniticStainlessSteel
∙C871MethodsforChemicalAnalysisofThermalInsulationMaterialsforLeachableChlorides,Fluoride,SilicateandSodiumIons
∙C892HighTemperatureFiberBlanketThermalInsulation
∙C929PracticeforHandling,Transporting,Shipping.Storage,ReceivingandApplicationofThermalInsulationMaterialsforUseinContactwithAusteniticStainlessSteel
∙C1055GuideforHeatedSurfaceConditionsThatProduceContactBurnInjuries
∙C1289FacedRigidCellularPolyisocyanurateThermalInsulationBoard
∙E84SurfaceBurningCharacteristicsofBuildingMaterials
∙E96TestMethodsforWaterVapourTransmissionofMaterials
2.2OtherCodesandStandards
Contractorshallensurethattheequipmentcomplieswiththerequirementsofallfederal,provincialandregionalacts,regulationsandordinances.AnyrequiredgovernmentalapprovalsshallbetheContractor’sresponsibility.
3.0definitionsofinsulation
Thefollowingdesignationshallbeusedtoidentifyinsulationandtracingonalldrawings,linelists,andotherdocuments,unlessotherwisenoted.
HC-Insulationforheatconservation
CI-Coldinsulationandanti-sweatprotection
PP-Personnelprotection
ST-SteamTraced
ET-ElectricTraced
GT-GlycolTraced
AllinsulationtermsanddefinitionsshallbeinaccordancewithASTMC168
4.0materials
4.1General
4.1.1Allinsulationmaterialsshallbesuitableforthetemperatureandserviceapplicationwithoutmechanical,chemicalorthermaldegradationorfailure.
4.1.2Allsuppliedmaterialsshallbenewandundamaged.Materialsshallbeprotectedfromweatherandothersourcesofdamageduringstorageandinstallation.
4.1.3Insulatingandsealingmaterials,includingcements,coverings,etc.,shallnotcontainasbestosandshallbenoncombustible.
4.1.4MaterialsubstitutionsshallbeapprovedbyOwnerpriortosupplyandinstallation.
4.2Insulation
4.2.1Generally,forheatconservationorpersonnelprotection,fiberglass,mineralwool,urethane,aerogelorcalciumsilicateinsulationshallbeused.
4.2.2InsulationsystemsforundergroundordirectburialapplicationsshallbeapprovedbythePurchaser.Theinsulationincombinationwithcorrosionprotectivecoatingsshallprotectthecarrierpipefromcorrosiveeffectsofpenetratinggroundwater.
Thematerialselectedshall:
∙Beimpervioustomoisturepenetration
∙Notcorrodecarrierpipe
Generally,cellularglassshallbeusedforthispurposebutpouredinplacegranularinsulationorothersystemsmaybeusedsubjecttoapprovalbytheOwner.
4.2.3Calciumsilicateoraerogelshallbeusedinareasoffoottrafficandinareaswherethereisapossibilityofinsulationdamage,aswellasforsteamapplications.
4.2.4Fluidimperviousinsulationshallbeusedonequipmenthandlingmaterialswhicharesubjecttoautoignition.
4.2.5Whereinsulationatpipesupportpointsmustsupportpipeload,theinsulationshallbeoftheloadbearingtype.
4.2.6Expansionjointfillershallbemineralwoolorfiberglassfibrousloosefill.
4.2.7InsulationusedtocoverstainlesssteelshallcomplywithATSMC795andshallhavelessthan600mg/lofleachablechlorides,andgreaterthan20mg/lofsodiumsilicateforeachmg/lofchloride.
4.2.8Spray-onurethanefoaminsulationshallbeusedonlywithwrittenapprovalofthePurchaser.
4.2.9Allinsulationmaterialsshallhaveaflamespreadclassificationnottoexceed25whentestedinaccordancewithASTME84.
4.2.10Preformedinsulationshallbeusedforcoveringpipeandpipefittings.
4.2.11Rigidblockinsulationforcoveringtanks,heatexchangers,vesselsandequipmentisgenerallypreferred.Loosepackinsulationshallnotbeused.
4.3BarriersorCladding
4.3.1Weatherbarriersshallbeappliedforalloutdoorinsulationapplicationsandwhereinsulation/watercontactispossible.
4.3.2Allowablemetalsforbarriersarealuminum,stainlesssteelandgalvanizedsteel.GalvanizedsteelshallonlybeusedwithwrittenapprovalbyOwner.
4.3.3Stainlesssteelinsulationjacketingshallbeused:
∙Inregionswhereprobabilityofpunctureordamagetothebarrierexists.
∙Overanyinsulationintendedasfireproofing.
4.3.4Metalweatherbarriershallbeaccordingtothefollowingminimumthicknessesforthermalservice:
∙Aluminum-0.40mm(26gauge)
∙GalvanizedSteel-0.25mm(31gauge)priortogalvanizing
∙AusteniticStainlessSteel-0.25mm(31gauge)
Aluminumandgalvanizedsteelcladdingshallhaveafactoryinstalledintegralcondensatebarrier.Thealuminumcladdingshallbe0.4mmthickforpipingandequipmentofnominaldiameter914mmorless.Forpipingandequipmentgreaterthan914mmdiameter,thealuminumcladdingshallbe0.5mmthick.
4.3.5ExceptasnotedhereinorotherwiseapprovedbyOwner,claddingforpipingandhorizontalequipmentshallbesmoothorembossedaluminum.Claddingonverticalequipmentshallbecorrugatedaluminum.
4.4Sealants,MasticsandCements
4.4.1Appliedcoatingsofasphaltic(mastic)orelastomeric(butylRubber)materialsshallcomplywiththefollowing:
∙Aflamespreadclassificationofnotmorethan25asperASTME84.
∙Shallberesistanttosolarradiation.
4.4.2MasticsandcoatingsshallconformtoASTMC647.
4.4.3Masticsforcoldconservationserviceshallbevapourproof(nonbreathing).Masticsforheatconservationserviceshallbemoistureproof(breathing).
4.4.4ThermalinsulatingcementshallconformtoASTMC195.
4.4.5Caulkingforsealingweatherbarriersshallbenon-shrinking,permanentlyflexibleandcompatiblew