格兰仕商用空调单元机技术手册科海电器培训手册.docx
- 文档编号:26824231
- 上传时间:2023-06-23
- 格式:DOCX
- 页数:57
- 大小:1.28MB
格兰仕商用空调单元机技术手册科海电器培训手册.docx
《格兰仕商用空调单元机技术手册科海电器培训手册.docx》由会员分享,可在线阅读,更多相关《格兰仕商用空调单元机技术手册科海电器培训手册.docx(57页珍藏版)》请在冰豆网上搜索。
格兰仕商用空调单元机技术手册科海电器培训手册
格兰仕单元式中央空调
科海电器培训手册
()
2009年第一版
目录
一、产品概述·························································4
1.产品特点························································4
2.命名规则························································4
3.低静压风管送风式空调机组概述····································5
a.外观图······················································5
b.性能参数·····················································5
c.内机结构图··················································10
d.室内机安装··················································10
e.室内机安装尺寸··············································13
4.中静压风管送风式空调机组概述···································14
a.外观图······················································14
b.性能参数····················································14
c.室内机安装尺寸··············································18
5.高静压风管送风式空调机组概述···································19
a.外观图······················································19
b.性能参数····················································19
6.四面出风嵌入式空调机组概述·····································22
a.外观图······················································22
b.性能参数····················································23
c.内机结构图··················································24
d.室内机安装··················································26
e.单元式中央空调外机底座尺寸··································29
f.单元式中央空调电缆线规格···································29
g.单元式中央空调电缆电线接线图································30
二、产品故障信息显示··················································38
三、方案设计和安装施工·················································39
1.方案设计························································39
2.安装施工························································47
3.排水施工························································57
4.保温施工························································62
5.风管制作和安装··················································64
一、产品概述
1.产品特点
单元式商用空调适用范围广泛,“一对一”的个性体现,充分满足不同用户的需求。
适用于高档营业厅、咖啡厅、餐厅的室内吊顶安装,典雅、舒适、倍添生活情趣。
可接入楼宇自控系统。
机身体积小,安装方便,大大缩短了空调的安装工期,超静音的运行。
2.命名规则
整机命名规则(制冷量≤14000W)
KFR-120T1W/SYZAL–B(520)
室外机系列设计号改进号
改进序号
配管形式:
L—长配管;常规配管省略
冷媒种类:
A—R410A;R22省略
进管方式:
Z—左进管;右进管省略
控制方式:
Y—遥控,X—线控
电源类型:
S—380V50Hz3N~;220V50Hz1N~省略
W—为室外机
室内机类型:
T1—高静压风管机;T2—中静压风管机;T3—标准静压风管机;Q1—一面出风天花机;Q2—两面出风天花机;Q4—四面出风天花机;G—挂壁式内机;D—座吊两用机;J—天井机
额定制冷量:
×100W。
R—热泵机型;RD—热泵+电辅;单冷机型省略
产品代号:
KF—单元式中央空调
整机命名规则(制冷量>14000W)
RF-25T1W/SYZAL–B
改进序号:
配管形式:
L—长配管;常规配管省略
冷媒种类:
A—R410A;R22省略
进管方式:
Z—左进管;右进管省
控制方式:
Y—遥控,X—线控
电源类型:
S—380V50Hz3N~;220V50Hz1N~省略
W:
为室外机
室内机类型:
T1—高静压风管式;L—立柜式
额定制冷量:
×100W。
产品类型:
LF—风冷冷风型;RF—风冷热泵型;
LFD—风冷冷风电热型;RFD—风冷热泵电热型;
3.低静压风管送风式空调机组概述
a.外观图
b.性能参数表
型号
KF-25T3W/Y
KFR-25T3W/Y
KFR(D)-25T3W/Y
制冷量(kW)
2.5
制热量(kW)
/
2.8
2.8+1.0
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
4.38
4.21
额定功率(kW)
0.915
0.88
制热
额定电流(A)
/
4.21
3.97(+4.6)
额定功率(kW)
/
0.83
0.83(+1.0)
标准风量m3/h(室内机)
430
静压(Pa)
30
噪音值dB(A)
室内机
38
室外机
51
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
815×490×240
室外机(宽×深×高)
665×295×505
质量(kg)
室内机
13.5
13.5(+0.5)
室外机
25
26
冷媒配管
气侧(mm)
Φ9.52
液侧(mm)
φ6.35
最长长度(m)
10
室内外机最大高度差(m)
5
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(电源线+信号线)
3×1.5mm2+3×1.5mm2
3×1.5mm2+5×1.5mm2
3×2.5mm2+5×1.5mm2
型号
KF-35T3W/Y
KFR-35T3W/Y
KFRD-35T3W/Y
制冷量(kW)
3.5
制热量(kW)
/
3.9
3.8+1.0
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
5.89
5.89
额定功率(kW)
1.23
1.23
制热
额定电流(A)
/
5.65
5.65+4.6
额定功率(kW)
/
1.18
1.18+1.0
标准风量m3/h(室内机)
550
静压(Pa)
30
噪音值dB(A)
室内机
40
室外机
53
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
815×490×240
室外机(宽×深×高)
840×310×510
质量(kg)
室内机
14.5
15
室外机
36
37
冷媒配管
气侧(mm)
Φ12.7
液侧(mm)
Φ6.35
最长长度(m)
10
室内外机最大高度差(m)
5
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(电源线+信号线)
3×1.5mm2+3×1.5mm2
3×1.5mm2+5×1.5mm2
3×2.5mm2+5×1.5mm2
型号
KF-50T3W/Y
KFR-50T3W/Y
KFRD-50T3W/Y
制冷量(kW)
5.0
制热量(kW)
/
5.5
5.5+1.5
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
8.52
8.56
额定功率(kW)
1.78
1.79
制热
额定电流(A)
/
8.33
8.33+6.8
额定功率(kW)
/
1.74
1.74+1.5
标准风量m3/h(室内机)
800
静压(Pa)
30
噪音值dB(A)
室内机
42
室外机
56
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1000×490×240
室外机(宽×深×高)
860×370×690
质量(kg)
室内机
17.5
17.5(+0.5)
室外机
49
50
冷媒配管
气侧(mm)
Φ12.7
液侧(mm)
Φ6.35
最长长度(m)
17
室内外机最大高度差(m)
7.5
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(电源线+信号线)
3×2.5mm2+3×2.5mm2
3×2.5mm2+5×2.5mm2
3×4.0mm2+5×2.5mm2
型号
KF-71T3W/Y
KFR-71T3W/Y
KFRD-71T3W/Y
制冷量(kW)
7.1
制热量(kW)
/
7.9
7.9(+2.0)
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
12.2
11.96
额定功率(kW)
2.55
2.5
制热
额定电流(A)
/
12.34
12.34+9.1
额定功率(kW)
/
2.58
2.58+2.0
标准风量m3/h(室内机)
1280
静压(Pa)
30
噪音值dB(A)
室内机
42
室外机
63
64
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1130×490×240
室外机(宽×深×高)
900×370×690
质量(kg)
室内机
18.5
18.5(+0.5)
室外机
63
64
冷媒配管
气侧(mm)
Φ15.88
液侧(mm)
Φ9.52
最长长度(m)
20
室内外机最大高度差(m)
10
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(外机电源线+信号线)\内机电源线(内外机电源线分开供电)
3×4mm2+2×1.5mm2
\3×1.5mm2
3×4mm2+4×1.5mm2
\3×1.5mm2
3×4mm2+4×1.5mm2
\3×2.5mm2
型号
KF-120T3W/SY
KFR-120T3W/SY
KFRD-120T3W/SY
制冷量(kW)
12.0
制热量(kW)
/
13.2
13.2(+3.0)
电源(电辅热)
380V3N~50Hz
电器特性
制冷
额定电流(A)
8.29
8.32
额定功率(kW)
4.69
4.71
制热
额定电流(A)
/
8.46
8.46+13.6
额定功率(kW)
/
4.79
4.79+3.0
标准风量m3/h(室内机)
1800
静压(Pa)
30
噪音值dB(A)
室内机
46
室外机
62
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1715×490×240
室外机(宽×深×高)
1030×415×955
质量(kg)
室内机
31
32
室外机
62
63
冷媒配管
气侧(mm)
Φ19.05
液侧(mm)
Φ9.52
最长长度(m)
25
室内外机最大高度差(m)
10
排水管(mm)
DN20
电线规格(外机电源线+信号线)\内机电源线(内外机电源线分开供电)
5×2.5mm2+2×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×2.5mm2
注:
1.制冷量测量的基于以下工况:
室内侧空气干球温度27度,湿球温度19度;
室外侧空气干球温度35度,湿球温度24度;
2.制热量测量的基于以下工况:
室内侧空气干球温度20度,室外侧空气干球温度7度,湿球温度6度。
上述各参数是在连接管长度为5m,水平连接的标准工况下测得。
由于产品性能的改善,上述参数可能会有所更改。
3.上表71和120机器的配线是内外机分开供电的。
在现场如果内机电源从外机接入的话,必须加大一号供外机的电源线径!
本公司保留因提高产品性能而变更产品设计恕不另行通知的权利,请以铭牌参数为准。
c.内机结构图
]
序号
零部件名称
数量
序号
零部件名称
数量
1
蜗壳组件
4
11
配管压板1
1
2
电机
2
12
配管压板2
2
3
电机安装压板
8
13
电控盒
1
4
电机支架
2
14
卸水板
1
5
电机安装架垫板
2
15
卸水板支撑板
1
6
右后侧板
1
16
蒸发器部件
1
7
中隔板
1
17
右前侧板
1
8
左后侧板
1
18
左前侧板
1
9
接水盘
1
19
电加热组件
2
10
配管支撑板
1
20
顶盖
1
d.室内机安装
(1)室内机的吊装
室内机的安装必须确保系统管路和风管的长度最短。
确保顶部吊杆有足够的强度承受机组的重量。
定好吊杆位置,与机组上的吊装孔对准后紧固。
检查机组安装后是否水平放置,并考虑按下图尺寸设置排水坡度(坡度大于1/100)。
(2)出风管的安装
出风管一般有矩形与圆形两种型式。
矩形风管可用铆钉直接与室内机出风口连接。
圆形风管需增加一个过渡风管和室内机出风口相连,另一端可单独或分流后与出风窗连接,其长度不超过6米为宜,如下图示,各出风口风速应调整到基本一致,以满足房间空气调节要求。
(3)回风管的安装
采用侧面进风时,需制作回风管,用铆钉连接在室内机回风口上,另一端与回风窗连接。
采用下进风时,另购或自治一段帆布风管呈折叠状,作为回风口与回风窗的过渡连接,这样可根据室内天花板高度自由调节,并且当机组运行时,帆布风管可防止天花板的震动。
如下图示。
(4)回风管与出风管安装提示
为减少传递过程中能量损失,及制冷时冷凝水的析出,回风管与出风管应有保温层如图示:
回风管与出风管应有铁支架固定在楼层预制板上,且风管的所有接口需用密封胶封严,回风管边缘距离建议在150mm以上。
冷凝水排水管的安装应保持1%以上倾斜度,排水管也应用保温套管保温。
室内机安装图
e、T3风管机室内机安装尺寸:
4.中静压风管送风式空调机组概述
a.外观图
型号
KF-50T2W/Y
KFR-50T2W/Y
KFRD-50T2W/Y
制冷量(kW)
5.0
制热量(kW)
/
5.5
5.5+1.5
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
9.0
8.76
额定功率(kW)
1.88
1.83
制热
额定电流(A)
/
9.0
9.0+6.8
额定功率(kW)
/
1.88
1.88+1.5
标准风量m3/h(室内机)
860
静压(Pa)
50
噪音值dB(A)
室内机
44
室外机
56
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
915×677×250
室外机(宽×深×高)
845×320×545
质量(kg)
室内机
24
25
室外机
49
50
冷媒配管
气侧(mm)
Φ12.7
液侧(mm)
Φ6.35
最长长度(m)
10
室内外机最大高度差(m)
5
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(电源线+信号线)
3×2.5mm2+3×2.5mm2
3×2.5mm2+5×2.5mm2
3×4.0mm2+5×2.5mm2
型号
KF-71T2W/Y
KFR-71T2W/Y
KFRD-71T2W/Y
制冷量(kW)
7.1
制热量(kW)
/
7.9
7.9(+2.0)
电源(电辅热)
220V~50Hz
电器特性
制冷
额定电流(A)
12.2
11.96
额定功率(kW)
2.55
2.5
制热
额定电流(A)
/
12.2
12.34
额定功率(kW)
/
2.58
2.58+2.0
标准风量m3/h(室内机)
1310
静压(Pa)
70
噪音值dB(A)
室内机
46
室外机
58
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1110×677×250
室外机(宽×深×高)
900×370×690
质量(kg)
室内机
28
29
室外机
63
64
冷媒配管
气侧(mm)
Φ15.88
液侧(mm)
Φ9.52
最长长度(m)
20
室内外机最大高度差(m)
10
排水管(mm)
DN20
控制方式
遥控(线控可选)
电线规格(外机电源线+信号线)\内机电源线(内外机电源线分开供电)
3×4mm2+2×1.5mm2
\3×1.5mm2
3×4mm2+4×1.5mm2
\3×1.5mm2
3×4mm2+4×1.5mm2
\3×2.5mm2
型号
KF-120T2W/SY-B
KFR-120T2W/SY-B
KFRD-120T2W/SY-B
制冷量(kW)
12.0
制热量(kW)
/
13.2
13.2+3.0
电源(电辅热)
380V3N~50Hz
电器特性
制冷
额定电流(A)
8.29
8.53
额定功率(kW)
4.69
4.83
制热
额定电流(A)
/
8.96
8.96+13.6
额定功率(kW)
/
5.07
5.07+3.0
标准风量m3/h(室内机)
1900
静压(Pa)
70
噪音值dB(A)
室内机
49
室外机
62
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1390×677×250
室外机(宽×深×高)
1030×415×955
质量(kg)
室内机
35
37
室外机
89
90
冷媒配管
气侧(mm)
Φ19.05
液侧(mm)
Φ9.52
最长长度(m)
25
室内外机最大高度差(m)
10
排水管(mm)
DN20
电线规格(外机电源线+信号线)\内机电源线(内外机电源线分开供电)
5×2.5mm2+3×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×2.5mm2
型号
KF-120T2W/SY-C
KFR-120T2W/SY-C
KFRD-120T2W/SY-C
制冷量(kW)
12.0
制热量(kW)
/
13.2
13.2+3.0
电源(电辅热)
380V3N~50Hz
电器特性
制冷
额定电流(A)
8.34
8.48
额定功率(kW)
4.72
4.72
制热
额定电流(A)
/
8.39
8.39+13.6
额定功率(kW)
/
4.8
4.8+3.0
标准风量m3/h(室内机)
1900
静压(Pa)
70
噪音值dB(A)
室内机
50
室外机
62
外观
室内机
镀锌钢板
面板颜色
/
外形尺寸(mm)
室内机(宽×深×高)
1309×677×250
室外机(宽×深×高)
975×410×1260
质量(kg)
室内机
35
37
室外机
106
冷媒配管
气侧(mm)
Φ19.05
液侧(mm)
Φ9.52
最长长度(m)
25
室内外机最大高度差(m)
10
排水管(mm)
DN20
电线规格(外机电源线+信号线)\内机电源线(内外机电源线分开供电)
5×2.5mm2+3×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×1.5mm2
5×2.5mm2+4×1.5mm2
\3×2.5mm2
注:
1.制冷量测量的基于以下工况:
室内侧空气干球温度27度,湿球温度19度;
室外侧空气干球温度35度,湿球温度24度;
2.制热量测量的基于以下工况:
室内侧空气干球温度20度,室外侧空气干球温度7度,湿球温度6度。
上述各参数是在连接管长度为5
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 格兰仕 商用 空调 单元 技术 手册 电器 培训