苏丹国电220kV电力变压器英文招标书
SECTION7
TECHNICALSPECIFICATION
Part6TRANSFORMERSANDREACTORS
BlueNileGrid
ThirdCircuitRoseires-Khartoum
Phase1,Roseires-Rank-Rabak
NATIONALELECTRICITYCORPORATION(NEC)
REPUBLICOFSUDAN
TABLEOFCONTENTS
Page
7.6TransformersandReactors
7.6.1GeneralInformation
ThispartoftheSpecificationscoversthedesign,manufacture,factorytesting,transport,delivery,erection,unloadingandstorageatsite,commissioningandhandingoverinsatisfactoryoperatingconditionofthepowertransformers,thedistributionandearthingtransformersaswellastheshuntreactors.
ThetransformersandreactorsshallbedesignedandarrangedinfullcompliancewithallapplicableSections,ArticlesandDrawingsoftheseSpecifications.
ThelatestissuesofRecommendationsoftheInternationalElectrotechnicalCommission(IEC-Standards),shallapplyinparticularaslistedbelow:
∙IEC60044
Instrumenttransformers
∙IEC60060
High-voltagetesttechniques
∙IEC60071
Insulationco-ordination
∙IEC60076
Powertransformers
∙IEC60085
Thermalevaluationandclassificationofelectricalinsulation
∙IEC60137
Insulatingbushingsforalternatingvoltagesabove1000V
∙IEC60214
On-loadtapchangers
∙IEC60270
Partialdischargemeasurements
∙IEC60289
Reactors
∙IEC60296
Specificationforunusedmineralinsulatingoilsfortransformersandswitchgear
∙IEC60354
Loadingguideforoil-immersedpowertransformers
∙IEC60529
Degreesofprotectionprovidedbyenclosures(IPcode)
∙IEC60542
Applicationguideforon-loadtap-changers
∙IEC60551
Determinationoftransformerandreactorsoundlevels
∙IEC60567
Guideforsamplingofgasesandoilfromoil-filledelectricalequipmentandfortheanalysisoffreeanddissolvedgases
∙IEC60599
Interpretationoftheanalysisofgasesintransformersandotheroil-filledelectricalequipmentinservice
∙IEC60616
Terminalandtappingmarkingsforpowertransformers
∙IEC60722
Guideforlightningimpulseandswitchingimpulsetestingforpowertransformersandreactors
∙IEC60726
Dry-typepowertransformers(whereapplicable)
∙IEC60815
Guideforselectionofinsulatorsinrespectofpollutedconditions
∙IEC60947
Low-voltageswitchgearandcontrolgear
SupplementarystandardsaretheinternationalStandardsISO,theGermanstandardsDINandVDE,theBritishstandardsBSortheirsubsequentEURONORMs,theAmericanstandardsorspecificnationalstandardsintheabovementionedsequence,iftherearenorelevantIEC-standardsexistingand/orifexplicitlyaskedforintheseTenderDocuments.
TheBiddershallsubmitwithhisofferalistofsimilartransformersand/orreactorsalreadydeliveredbythemanufacturerproposed.InadditiontheBiddershallsubmitwithhisoffervalidcertificatesprovingthattheproposedmanufacturersarecertifiedbyISO9001.Manufacturersnothavingsufficientexperienceinmanufacturingandtestingofsimilartransformersand/orreactorslikethoseasspecifiedand/ornotbeingcertifiedbyISO9001willnotbeaccepted.
Eachitemwhichisobviouslynecessaryforproperfunctionandcompletionofthework,whetherespeciallyspecifiedintheTenderDocumentsornot,istobeincludedinthetenderprice.
7.6.2PowerTransformers
7.61.2.1General
Thedesignofthepowertransformersshallbebasedonthefollowingconditionsandrequirements:
∙Thedesignshallbebasedonthesiteandserviceconditions;ambienttemperature:
maximum50°C,averageofthehottestmonth40°C,yearlyaverage30°C
∙Themaximumpermissibletemperatureriseofthetransformeroil(topoil)shallnotexceed45K,andtheaveragetemperatureriseofthewindingistobelimitedto55K(hotspotmax.68K,hotspotfactor:
1.3).Thisisapplicableforalltapchangersettingsandallforcedcoolinginoperation
∙Thehottestspottemperatureat115%excitationandforcyclicloadingdutiesasperIEC60354shallnotexceedthelimitsasspecifiedintheTechnicalDataSheetsoftheseSpecificationsunderthermalsteadystateconditions
∙Thetransformers,completelyassembledwithbushings,cableboxesand/orflangeconnections,shallbedesignedandconstructedtowithstandwithoutdamagestheeffectsofshortcircuitsasperIEC60076-5foratleast3secondsatratedconditionsandafterallloadingconditionsasspecifiedinIEC 60354
∙Thetransformersshallbedesignedwithparticularattentiontothesuppressionofharmonicvoltagestoeliminatewaveformdistortionandfromanypossibilityofhighfrequencydisturbancesreachingsuchamagnitudetocauseinterferencewithcommunicationcircuits
∙Built-inshortcircuitlimitingreactors,ifany,shallnotbeinstalledinaseparatetankappendedtothemaintank
∙Neutralpointsshallbebroughtoutbysuitablemeansandshallbegrounded
∙Theopendeltaofstabilisingwinding,ifany,shallbebroughtoutbyoutdoorbushingsandshallbeshortenedandgroundedbysolidcopperbarsrigidlysupportedandfastened
∙InsulationoilusedforallpowertransformerandshuntreactorstobedeliveredforthesamesubstationshallbeofthesameoilmanufacturerandtypeandshallbeinfullcompliancewiththerelevantArticlesbelow
Furthermore,eachtransformershallcomplywiththestipulationsofthefollowingArticles.
7.61.2.2Windings
AlltransformerwindingsforLI:
350kV/AC:
140kVandbelowshallhaveuniforminsulation.Transformerwindingsdesignedforhigherinsulationlevelsmayhavenon-uniforminsulation.InthesecasestheratedACinsulationlevelforneutralpointsshallbeatleast95kV.
Duetothepossibilityofhightransferredover-voltagesnoneofthewindingsshallbedesignedforlessthanLI:
125kV/AC:
50kV.
ParticularvaluesforallinsulationandtestlevelsshallbeobtainedfromtheTechnicalDataSheetsoftheseSpecifications.
Built-inseriesreactors,ifprovided,areonlypermittedtobeconnectedin-linewiththeleadstotheentrancesofdelta-connectedtertiarywindings,andtheyshallbedesignedandarrangedwithparticularattentiontokeepalltransferredover-voltagesaslowaspossibleandtoavoidseriousresonances.Built-inneutralgroundingreactorswillnotbeaccepted.
Allwindingsandtheirleadsshallbedesignedandarrangedsuchastowithstandallkindsoftransferredover-voltages.Protectivecapacitorsshallnotbeprovidedforanyofthewindings.Non-linearZnOprotectiveelementsinanywindingsotherthanregulationwindingswillnotbeaccepted.
Windingsshallbeofbestmoderndesignwithconductorshavingconstantcross-sectionalongthewholewindings.Electrolyticcopperofahighconductivityandinsulationmaterialofhighqualityshallbeused.
Theinsulationmaterialofwindingsandconnectionsshallbefreefrominsulationcompoundssubjecttosoftening,shrinkingorcollapsingduringservice.Moreover,noneofthematerialusedshalldisintegrate,carboniseorbecomebrittleundertheactionofhotoil,underallspecifiedloadconditions.
ThecoilsmustbecapableofwithstandingmovementanddistortioncausedbyalloperatingconditionsasspecifiedinIEC60354.Adequatebarriersshallbeprovidedbetweenwindingsandcoreandbetweenthewindings.Allleadsorbarsfromthewindingstotheterminalboxesandbushingsshallberigidlysupported.Stressesoncoilsandconnectionsmustbeavoided.
Toincreasethecapabilityofthetransformersofwithstandingthestressesundershort-circuitconditionsmoderntechnologyindesignandconstructionshallbeapplied(e.g.lowcurrentdensities,andpre-dryingandpre-compressingofthewindingsbeforemountingontothecore,etc.).
Regulationwindingsfordeltaconnectedwindingsshallbeprovidedinmid-windingconnectiononly,unlessspecifiedotherwiseintheTechnicalDataSheets.
Thevaluesforimpedancevoltagesonextremetappingsshallnotdeviatefromthoseforprincipaltappingsbyapercentagevalueofmorethantwothirdofthedifferenceinpercentagetappingfactorbetweentheconcernedtappingsandtheprincipaltappings,andthetransformersshallhavethehighestlossesatthehighestcurrenttaps(lowestvoltagetaps).
7.61.2.3MagneticCore
Themagneticcoreshallbeofthecore-formtypeandshallbemadeoflaminationsofnon-ageing,cold-rolled,grain-oriented,siliconsteelofhighpermeability(Hi-B-type;W17/50:
max.1.05W/kg)withoutburrs(particularvaluesinaccordancewiththeTechnicalDataSheetsoftheseSpecifications).Anykindofshell-formcoreisnotacceptable.
UnlessspecifiedotherwiseintheTechnicalDataSheetsthemaximummagneticfluxdensityinthelegsandyokesofthecoreshallnotexceed1.65Teslaatratedvoltageandfrequency.ParticularvaluesshallbeobtainedfromtheTechnicalDataSheetstheseSpecifications.Eachlaminationshallbeinsulatedwithhighqualityinsulationcoating.
Thejointsoflimbsandyokesshallbedesignedandconstructedtokeeptheno-loadlossesandthehotspottemperatureinthemagneticcoreaswellasthenoiselevelaslowaspossiblebyapplicationofthestep-lapcore-stackingmethod.
Thecoreanditsclampingplatesshallformarigidunitstructurewhichshallmaintainitsformandpositionundertheseverestressesencounteredduringshipment,installationandshortcircuits.Careshallalsobetakentosecureuniformlydistributedmechanicalpressureoverallthelaminationstopreventsettingofthecoreandtolimitnoiseandvibrationstoaminimumunderserviceconditions.
Inordertopreventclosedmagneticcircuitviathetank,thetopmaincoreclampingstructureshallnotbeconnectedtothetankcover.Themagneticcoreshallbeearthedtothetankcoveratonepointonlythroughremovablelinksinanappropriateterminalbox,p
- 配套讲稿: