谐波测试分析报告参考样本
测试报告
委托单位:
检测项目:
谐波测试
报告日期:
温州清华电子工程有限公司测试组
送:
一、测试目的…………………………………………………………2
二、测试依据…………………………………………………………2
三、测试内容…………………………………………………………3
四、测试信号与接线方式……………………………………………3
采样信号……………………………………………4
测试工况……………………………………………4
接线方式………………………………………………4
测试时间…………………………………………………4五、测试结果……………………………………………………5
六、结论…………………………………………………………8
附件测试数据
1
一、测试目的
XXXXXXX一家工程用塑料管材制造商,是国内从事PP-R管道的龙头企业,目前35KV变电所共有3台主变,1#,2#主变容量为1250KVA,采用并联运行方式,3#主变容量为1600KVA,分别供挤出,注塑,波纹管,破碎造粒车间的供电,而大部分的电机都采用直流调速,工作时不同程度的产生谐波注入35KV母线,故通过对伟星新型建材有限公司三台主变0.4KV侧的谐波测试,了解该变低压母线上的谐波情况,来评估0.4KV级别电源的电能质量是否符合国标《GB14549-93电能质量公用电网谐波》。
二、测试依据
¾GB14549-93《电能质量公用电网谐波》
表1公用电网谐波电压(相电压)限值
电网标称电压电压总谐波畸变各次谐波电压含有率%
KV率%奇次偶次
0.385.04.02.0
6
10
4.03.21.6
35
66
3.02.41.2
1102.01.60.8
表21250KVA0.4KV公用电网谐波电流限值
谐波次数5711132325
允许值1299158502925
表31600KVA0.4KV公用电网谐波电流限值
谐波次数5711132325
允许值16511875643732
谐波电流允许值计算见GB14549-93中公司(B1),其中变压器1600KVA,短路容量为26.7MVA,1250KVA,短路容量为20.8MVA。
¾GB/T12326-2000《电能质量电压波动和闪变》
电力系统公共连接点,由波动负荷产生的电压变动限值和变动频度、电压等
级有关,如表3。
表4电压变动限值
频度r,h-1
电压变动限值d,%
LV、MVHV
r≤143
1<r≤1032.5
10<r≤100221.5
100<r≤10001.251
2
注:
LV(低压)Un≤1kV;MV(中压)1kV<Un≤35kV;HV(高压)35kV<Un≤220kV
三、测试内容
—0.4KV母线滤波器切除时电压畸变率
—0.4KV母线滤波器切除时电压波动
—0.4KV母线滤波器切除时电流谐波含量
—0.4KV母线滤波器切除时三相功率
—0.4KV母线滤波器投入时电压畸变率
—0.4KV母线滤波器投入时电压波动
—0.4KV母线滤波器投入时电流谐波含量
—0.4KV母线滤波器投入时三相功率
四、测试信号与接线方式
‹系统图
3
‹采样信号
项目
测试点测试点名称采样信号采样点测试仪器备注
测试点1
1,2,3#主
变0.4KV侧
A,B,C,N,GND电压信号
A,B,C电流信号
0.4KV采样
0.4KVCT二次端FLUKE435间隔
5S
‹测试仪器:
F435
*记录三相系统中所有的电能质量参数
*工业现场使用最高的安全等级
*四个电压通道和四个电流通道
*同时在所有相线上捕获波形数据
*系统监测:
一个仪表器上实现全部电能质量参数*自动显示瞬态尖峰脉冲信号
*自动趋势绘图功能
*强大的FLKUKEVIEW软件功能
*专业的电能质量报告
‹接线方式:
三相四线
‹测试时工况
测试时1,2,3#主变都处于正常生产中,三台主变电容补偿柜全部投入运行(普通电容投入会引起飞系统谐波放大)
2007-10-2413:
20至13:
50电容柜投运时1#主变0.4KV电能情况2007-10-2413:
57至14:
27电容柜投运时2#主变0.4KV电能情况2007-10-2414:
49至15:
17电容柜投运时3#主变0.4KV电能情况‹测试时间
4
2007-10-2413:
20至15:
17
五、测试结果
92007-10-2413:
20至13:
50电容柜投运时1#主变0.4KV谐波电容柜投运电压,电流图
电容柜投运谐波电压,电流及功率图
电容投运时谐波情况表
电容柜投运
谐波谐波电压(%)谐波电流(A)
次数U(a)U(b)U(c)I(a)I(b)I(c)国标
1215215.3216.6123512781299
30.120.150.1415.5810.7916.07128.9
56.546.566.34315.4347.5322.34128.9
74.674.384.59163.7152.37165.6591.5
THD(%)8.3058.6768.181----
功率因数0.92
备注:
红色字体为超标项,详见附表
上表可以看出当电容投入运行时引起谐波放大,谐波电压总畸变率达到
8.3%左右,超出国标值5%,谐波电流以5,7为主。
5
92007-10-2413:
57至14:
27电容柜投运时2#主变0.4KV谐波电容柜投运电压,电流图
电容柜投运谐波电压,电流及功率图
电容投运时谐波情况表
电容柜投运
谐波谐波电压(%)谐波电流(A)
次数U(a)U(b)U(c)I(a)I(b)I(c)国标
1215.4215.3216.7147815881505
31.141.171.2521.712.0416.5128.9
57.267.817.06387.1405.3372128.9
74.644.144.51175.86156.03171.291.5
THD(%)8.939.2168.787----
功率因数0.92
备注:
红色字体为超标项,详见附表
上表可以看出当电容投入运行时引起谐波放大,谐波电压总畸变率达到
8.8%左右,超出国标值5%,谐波电流以5,7为主。
6
92007-10-2414:
49至15:
17电容柜投运时3#主变0.4KV谐波电容柜投运电压,电流图
电容柜投运谐波电压,电流及功率图
电容柜投运时谐波情况表
电容柜投运
谐波谐波电压(%)谐波电流(A)
次数U(a)U(b)U(c)I(a)I(b)I(c)国标
1222.2222.7222.9925934.2885.23
30.220.30.3016.847.229.03165.5
51.751.681.9155147.4149.8165.5
70.680.670.8327.8828.2532.55117.5
THD(%)5.4225.1754.3----
功率因数0.92
备注:
红色字体为超标项,详见附表
上表可以看出当电容投入运行时引起谐波放大,谐波电压总畸变率达到5%左右,A,B相超出国标值5%,谐波电流以5,7为主。
7
六、结论
2007-10-24对XXXXXXXXXX三台主变的谐波进行了详细的测试,经过分析,结论如下:
(1)2007-10-2413:
20至13:
50电容柜投运时1#主变0.4KV谐波
谐波电压总畸变率达到8.3%左右,超出国标值5%,谐波电流以5,7为主,5次达到320A,7次160A。
(2)2007-10-2413:
57至14:
17电容柜投运时2#主变0.4KV谐波
谐波电压总畸变率达到8.8%左右,超出国标值5%,谐波电流以5,7为主,5次达到387A,7次170A。
(3)2007-10-2414:
49至15:
17电容柜投运时3#主变0.4KV谐波
谐波电压总畸变率达到5%左右,A,B相超出国标值5%,谐波电流以5,7为主,5次达到150A,7次40A。
1,2#主变负载最大电流可以达到2400A,故到时0.4KV母线谐波情况比目前还要严重;3#主变目前负荷比较小,公司已拟新增生产车间,由3#主变供电,到时3#主变电流增大,如果生产线含有直流调速电机等设备,谐波电流含量势必会增大。
从低压侧的谐波测试数据表明,三台主变在投入电容的情况下,0.4KV侧谐波电压,电流达不到国家标准值。
8
监控时间:
2007-10-2413:
20到:
2007-10-2413:
50
电压等级:
0.22KVPT:
1CT:
400
基准短路容量:
10MVA
用户协议容量1.25MVA
最小短路容量:
20.7999992MVA
供电设备容量:
1.25MVA
FLUKE435-电压谐波分析测试报告
工况:
1#变谐波电压
A
参数最大值最小值
相
平均值95%值最大值
B相
最小值平均值95%值
C相
最大值最小值平均值
国标值(%)
95%值合格
基波电压(V)216.232212.413214.252215.089216.103213.060214.486215.326217.290214.614215.854216.599
20.130%0.070%0.097%0.120%0.180%0.080%0.122%0.150%0.160%0.100%0.125%0.140%2.00%TRUE
31.200%0.740%0.928%1.060%1.260%0.930%1.082%1.190%1.320%1.010%1.146%1.230%4.00%TRUE
40.200%0.070%0.126%0.160%0.200%0.060%0.121%0.150%0.200%0.090%0.129%0.150%2.00%TRUE
57.280%5.620%6.014%6.540%7.670%5.950%6.563%7.110%6.800%5.200%5.771%6.340%4.00%FALSE
260.220%0.070%0.129%0.160%0.200%0.060%0.133%0.190%0.190%0.050%0.117%0.160%2.00%TRUE
至75.330%1.280%2.434%4.670%5.090%1.470%2.572%4.380%5.220%1.320%2.460%4.590%4.00%FALSE
2580.110%0.040%0.077%0.100%0.120%0.060%0.094%0.110%0.130%0.060%0.085%0.110%2.00%TRUE
次90.850%0.430%0.617%0.750%0.890%0.460%0.646%0.800%0.910%0.450%0.577%0.800%4.00%TRUE
谐100.120%0.040%0.079%0.100%0.120%0.030%0.067%0.090%0.120%0.040%0.077%0.100%2.00%TRUE
波111.560%0.580%1.143%1.490%1.830%0.710%1.426%1.740%1.820%0.970%1.456%1.720%4.00%TRUE
电120.050%0.020%0.034%0.040%0.060%0.020%0.045%0.060%0.050%0.020%0.034%0.040%2.00%TRUE
压130.220%0.030%0.109%0.190%0.500%0.030%0.175%0.310%0.360%0.030%0.113%0.300%4.00%TRUE
含140.090%0.040%0.051%0.060%0.090%0.030%0.051%0.060%0.090%0.030%0.052%0.060%2.00%TRUE
有150.380%0.200%0.301%0.350%0.400%0.250%0.329%0.380%0.390%0.130%0.283%0.360%4.00%TRUE
率160.050%0.020%0.035%0.050%0.050%0.020%0.031%0.040%0.050%0.020%0.032%0.040%2.00%TRUE
(%)170.390%0.040%0.207%0.380%0.220%0.040%0.133%0.210%0.510%0.210%0.330%0.450%4.00%TRUE
180.030%0.010%0.019%0.020%0.030%0.010%0.019%0.020%0.040%0.010%0.026%0.030%2.00%TRUE
190.110%0.040%0.076%0.100%0.110%0.020%0.065%0.100%0.080%0.020%0.051%0.070%4.00%TRUE
200.040%0.020%0.021%0.030%0.020%0.010%0.019%0.020%0.030%0.010%0.017%0.020%2.00%TRUE
210.200%0.070%0.147%0.190%0.200%0.060%0.140%0.180%0.170%0.040%0.105%0.140%4.00%TRUE
220.040%0.020%0.034%0.040%0.030%0.010%0.022%0.030%0.020%0.010%0.016%0.020%2.00%TRUE
230.180%0.050%0.115%0.170%0.090%0.040%0.065%0.080%0.100%0.030%0.064%0.090%4.00%TRUE
240.050%0.020%0.040%0.050%0.040%0.020%0.029%0.040%0.020%0.010%0.016%0.020%2.00%TRUE
250.080%0.040%0.060%0.070%0.080%0.020%0.056%0.080%0.070%0.030%0.051%0.060%4.00%TRUE
电压总畸变率%9.305%5.862%6.701%8.305%9.547%6.264%7.319%8.676%8.951%5.571%6.589%8.181%5.00%FALSE
0
监控时间:
2007-10-2413:
20到:
2007-10-2413:
50
电压等级:
0.22KVPT:
1CT:
400
基准短路容10MVA
用户协议容1.25MVA
最小短路容量:
20.7999992MVA
供电设备容量:
1.25MVA
FLUKE435-电流谐波分析测试报告
工况:
1#变谐波电流
A相B相C相
参数最大值最小值平均值95%值最大值最小值平均值95%值最大值最小值平均值95%值国标值合格
波电流(A1334.9461041.2341160.1091235.5271449.5851144.2111278.8111361.8271390.4871093.8101222.7441298.974
211.0624.3006.7308.12611.4424.1517.3028.66811.9084.9997.7459.085162.240TRUE
319.8429.16712.90215.58613.6265.0528.20710.78918.7836.41512.99316.069128.960TRUE
410.9562.4616.2598.47010.9162.7276.4168.46410.9492.6636.3178.25381.120TRUE
5343.505268.142290.207315.384375.557295.559320.710347.439345.667274.235297.117322.339128.960FALSE
268.2972.2454.6296.0348.3212.2985.1457.1087.8392.2394.7686.53654.080TRUE
至7184.08945.73184.898163.711175.98049.30587.500152.368184.79651.55491.210165.65491.520FALSE
2583.7191.8812.6883.2383.3941.7912.5603.0693.7871.7752.6233.32739.520TRUE
次96.3592.2843.6354.9617.3611.7664.3886.56110.4291.4872.8876.35243.680TRUE
谐103.2510.9622.0072.5742.7620.8641.5931.9733.1110.9961.9582.53833.280TRUE
波1136.47216.23627.78334.99845.82418.24836.67144.72841.51221.40832.85139.32858.240TRUE
电121.0550.3190.6850.8491.2030.3610.8311.0661.2460.3420.7751.00727.040TRUE
流136.8681.0082.2773.9197.2260.6403.0605.1416.3960.4461.9204.96849.920TRUE
含141.3750.4250.8050.9881.6540.4870.9091.1721.5860.5550.8971.13022.880TRUE
量151.3750.3880.8601.1572.5540.3821.2522.2231.7250.4861.0071.36824.960TRUE
(A)160.8020.3150.5270.6170.8900.3430.5100.6660.8710.3330.5680.75120.176TRUE
174.4981.0842.5694.0964.2231.4542.5043.5676.0192.1153.6595.27237.440TRUE
180.3690.2100.2560.3600.4110.1170.2590.3910.5170.2190.3370.39717.888TRUE
190.8230.3430.5280.7110.6860.2390.4120.5341.0490.2450.4940.75133.280TRUE
200.4650.1290.2710.4320.3800.1160.2330.3600.4840.1210.2640.37616.224TRUE
210.7810.2330.4670.6940.7840.1200.3140.4090.7410.2320.4090.61718.512TRUE
220.3690.1060.2320.3540.2710.1140.1450.2600.3880.1110.2450.37314.768TRUE
230.8690.2100.5360.8160.6750.3660.5190.6080.4910.2380.3370.46429.120TRUE
240.3820.1050.2830.3670.2760.1140.1730.2690.3910.1110.2580.37913.520TRUE
250.6670.3380.4550.5530.4090.1270.2930.3980.5710.2420.3970.48424.960TRUE
1
监控时间:
2007-10-2413:
57到:
2007-10-2414:
27
电压等级:
0.22KVPT:
1CT:
400
基准短路容量10MVA
用户协议容量1.25MVA
最小短路容量:
20.799999MVA
供电设备容量:
1.25MVA
FLUKE435-电压谐波分析测试报告
工况:
2#主变谐波电压
A相B相C相国标值
参数最大值最小值平均值95%值最大值最小值平均值95%值最大值最小值平均值95%
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 谐波 测试 分析 报告 参考 样本