2004)
建筑给水硬聚氯乙烯管道设计与施工验收规程>
(CECS41:
2004)要求施工
1.1.6Besidethisspecification,theconstructionshouldalsoconformtothefollowingcodes:
.Codeforconstructionandacceptanceofwatersupplyandseweragepipelineengineering(GB50268-97)
TechnicalspecificationofPVC-Upipewaterforbuildingdrainage(CJJ/T29-98)
TechnicalspecificationforburiedPEpipelineofsewerengineering(CECS164:
SpecificationfordesignandconstructionofUPVCforwatersupplyinbuildings(CECS41:
1.2设计依据:
1.2Codesfordesign
1.2.1<
建筑给水排水设计规范>
(GB50015-2003)
1.2.2<
建筑设计防火规范>
(GB50016-2006)
1.2.3<
建筑灭火器配置设计规范>
(GBJ50140-2005)
1.2.1Codefordesignofoutdoorwatersewerage(GB50015-2003)
1.2.2Codeofdesignonbuildingfireprotectionandprevention(GB50016-2006)
1.2.3Codefordesignonbuildinghydrantlayout(GBJ50140-2005)
1.3一般说明
1.3Normalnote
1.3.1尺寸单位:
管道长度和标高以m计,其余以mm计。
1.3.1Dimensionunit:
mforthepipelengthanditshigh,mmfortheothers.
1.3.2本工程室内首层地面±
0.000同建筑专业.
1.3.2The±
0.000of1stfloorofthebuildingsisthesameasoneshowedinthearchitecturedrawings.
1.3.3管道标高的表示法:
所注管道标高,均以室内首层地面±
0.000作基准推的相对标高.给水管道的标高是指管中心线的标高;
排水管道的标高是指管道内顶面的标高.
1.3.3Thenotedpipeheightisrelativeheightbasedonthe±
0.000of1stfloorofthebuildings,theheightofthesupplywaterpipeismeteredfromitscenterline,andtheonefordrainpipeismeteredfromthetopoftheit.
1.3.4除设计图中已有安装大样外,一般卫生设备均参照《全国通用给水排水标准图集99S304卫生设备安装》进行安装.
1.3.4Allsanitationshouldbeinstalledaccordingtothe“nationwatersupplyanddrainagestandarddrawingsselection99S304—sanitationinstallation”
1.3.5室内生活给水管道,其横管安装时宜有0.002-0.005的坡度坡向泄水装置。
1.3.5Aboutthewatersupplywaterpipeforlifethehorizontalpipeshouldbeinclinedtothedrainingdirection.
1.3.6给水管道上各种阀门必须检验合格后才安装,原则上当DN<
50时用截止阀,DN≥50时用闸板阀或蝶阀,但在环状管网上闸门及各种排空泄水阀一律用闸板阀或蝶阀.
1.3.6Beforetheinstallationallvalvesshouldbechecked,normallyadoptglobevalvewhileDN<
50mmandgatevalveorbutterflyvalvewhileDN≥50,exceptthatvalveorbutterflyvalveshouldbeadoptedaboutthevent&
drainvalvesonthecircularpipenet.
1.3.7室内排水立管上的检查口,底层和有卫生器具的最高层必须设置,如屋顶为上人平屋顶,能用立管伸顶通气管口清通时,顶层可不设检查口,其它每隔一层(6.0m左右)设置,检查口高出地面一般为1.0m,且应高出该层卫生器具上边缘150mm。
1.3.7Checkholesshouldbesetontheindoorverticaldrainpipeespeciallyinthe1stfloorandthehighestfloorwheretherearesomesanitarywaresinit,butintheaccessibleroof,ifcheckcanbedonethrutheventhole,checkholeneedn’tsetthere.Abouttheothercasecheckholeshouldbesetforeachfloor,anditshouldbe1.0mabovethefloorsurfaceand150mmabovethehighestoftheedgeofthesanitarywares.
1.3.8排水管道的横管与立管的连接应采用45°
的三通或45°
四通和90斜三通或90°
斜四通,立管底部与排出管连接处,应采用两个45°
弯头或采取弯曲半径不少于4倍管径的90°
弯头。
1.3.8Theconnectionjointbetweenthehorizontaldrainpipeandverticaldrainpipeshouldadoptedoneoftheoptions:
45°
3-wayjoint,45°
4-wayjoint,90°
3-wayrampjoint,90°
4-wayrampjoint,atthejointbetweenthebottomoftheverticaldrainpipeandtheoutletpipetwo45°
elbowsshouldbeadoptedorthebendradiusismorethan4timesoftheDN.
1.3.9所有卫生器具自带或配置存水弯,其水封深度不得小于50mm。
1.3.9Waterlockshouldbesetforallthesanitarywaresorthesanitarywaresshouldhavebeencompletewithwaterlockwiththem,andthedepthofthewaterlockshouldbemorethan50mm.
1.3.10管道支架要求
1.3.10Piperack
i衬里镀锌管.钢管水平安装支架间距不得大于下表:
iForthehorizontalzincingpipe,thedistancebetweenpiperacksshouldlessthanthelengthasfollowinglist.
公称直径
DN.mm
15
20
25
32
40
50
70
80
100
125
150
200
Max.distance支架最大间距mm
Insulated
保温管
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
6.0
7.0
Uninsulated不保温管
5.5
6.5
8.5
ii金属管材的给水及热水立管管卡安装要求:
iiForallmetalpipesofwatersupplyandhotwaterverticalpipestheirclipsshouldmeetthefollowingdemands:
a.层高H<
5m每层设一个.
a1pipeclipshouldbesetforeachflooriflayerH<
5m;
b.层高H≥5m每层设二个.
b2pipeclipsshouldbesetforeachflooriflayerH≥5m;
iii硬质塑料管,铝塑复合管支架最大间距如下表
iiiForthehardplasticpipeandAL-plasticpipe,thedistanceshouldbelessthanthelengthasthefollowinglist:
外径Outerdia.(mm)
45
75
支架最大间距
Max.distancemm
立管Vertical
1.20
1.50
2.00
横管Horizontal
0.4
0.5
0.75
1.10
iv承插塑料管管材插入管件承口的深度不得小于下表:
ivForthesocketplasticpipesocketdepthshouldnotlessthanthedepthasthefollowinglist:
外径Outerdia.(mm)
110
160
管端插入承口深度Socketdepth(mm)
60
第2章管道的选材防腐及试压
Chapter2Material、antisepticandpressuretestforthepipeline.
2.1生活给水(水)系统
2.1Thewatersupplysystemforlife
2.1.1室内管道采用:
提取车间给水管、热水管均采用热镀锌钢管,其余厂房采用PPR管。
洁净厂房内暴露在外的管道采用不锈钢管。
2.1.1Fortheindoorwatersupplypipehotzincingpipeshouldbeadoptedfortheextractingworkshopwatersupplypipesandthehotwatersupplypipes,thepipesintheotherbuildingshouldadoptPPRpipe.ButthepipeexposedinthecleanzoneshouldadoptSS(stainlesssteel)pipe.
2.1.2管道接口形式
2.1.2Typeofthepipejoint
i衬里镀锌钢管用衬里镀锌配件
iLiningzincingpipeshouldadoptliningpipefittingsasthejoint;
iiPPR塑料管专用粘合剂粘接.
iiPPRpipeconnectionshouldadoptspecbond.;
iii不锈钢管焊接或法兰连接.
iiiSSpipeconnectionshouldadoptweldingorflange.
2.1.3管道试验水压力:
(以首层室内地面作计算基准点)
2.1.3Thewaterpressuretestforthepipeline(basedonthe±
0.000ofthe1stfloor)
管道试验水压力为工作压力的1.5倍,但最小不少于0.6MPa,本工程采用0.9MPa.
Thetestpressureshouldbe1.5timesoftheworkingpressureandnotlowerthan0.6MPa,itis0.9MPainthisproject.
2.1.4所有管道均暗装于管道井内,吊顶内,墙内或采用建筑局部装修包封处理.
2.1..4Allthepipesshouldbeinstalledintheonespaceoffollowingoptions:
pipewell,interlayer,inwalls,partialspaceclosedpackedwithPPRsandwichpanel.
2.1.5室内给水管及卫生洁具的连接管道在穿过楼板或剪力墙时应配合土建施工预留孔洞.
2.1.5Wheretheindoorwatersupplypipeandthepipesconnectingthesanitarywaresperforatethefloorslabprearrangedholeshouldbepreparedcooperatingwithbuildingstructureconstruction.
2.2消火栓给水系统
2.2Firewatersupplysystem
2.2.1管材.热镀锌钢管
2.2.1Pipehotzincingtube
2.2.2管道接口形式
2.2.1Typeofthepipejoint
i镀锌钢管,衬里镀锌管
izincingpipe,liningzincingpipe
a管螺纹接口(DN<
=80mm)
apipejointwiththread(DN≤80mm)
b焊接(DN>
80mm)
bwelding(DN>
2.2.3管道试验水压力:
2.2.3Testpressureofthepipewaterpressuretest
消防管道的水压力是以消防水泵的最高压力(即流量为0时的扬程)来计算,当水泵最高压力小于0.6MPa时,试验压力为1.5倍;
当水泵最高压力大于0.6MPa时,试验压力为其压力加上0.3MPa;
当室内消火栓系统有消防水泵结合器时,试验压力还必须不小于1.4MPa,本工程为1.4MPa。
Thetestpressureiscalculatedbasedonthemax.pressureofthepump(thepumpliftat0waterflow),whenthemax.pressureislessthan0.6MPa,thetestpressureshouldbe1.5timesofit;
whenthemax.pressureismorethan0.6MPa,thetestpressureshouldbe0.3MPaplusit;
andwhenthereiswaterpumpconnectorthetestpressureshouldnotless1.4MPa,thetestpressureforthisprojectis1.4MPa.
2.2.4消防箱
2.2.4Hosecabinet
i单栓消防箱内的配备及要求:
iSingle-hydranthosecabinetshouldcompletewithfollowingparts
a室内消火栓一个,口径为DN65
aonehydrantwhichcaliberisDN65;
b直流水枪一支DN65X19
bonewatergunDN65X19
注:
在消防电梯前室的消火栓要用开花水枪
note:
c消防龙带:
口径为DN65
chosewhichcaliberis65
材质:
衬胶
material:
rubber-liningcanvas
工作压力:
1.0MPa
workingpressure:
1.0MPa
长度及条数:
25m1条
one25mlongofhose
d消防软管卷盘(配在消防箱内)一套口径DN19mm,长度20m
donecoilingplateforhose,whichcaliberis19and20mlong
e破玻璃手动报警器,电铃,指示灯各一个.
eoneglassmanualannunciator,oneelectricalbell,oneindicatorlight
2.3生活排水
2.3Domesticsewage
2.3.1室内管道采用硬质聚氯乙烯管,但有排水温度>
45°
C的工序排水管采用PPR管。
2.3.1DomesticsewagepipeshouldadopthardPVC,butifitsdrainsewagetemperatureishigherthan45°
CthepipeshouldadoptPPRpipe.
2.3.2管道接口形式:
2.3.2Typeofthepipejoint
承插排水塑料管的接口,应用粘接剂粘牢.粘接剂的理化性能必须符合产品说明和设计要求
Forthesocketdrainplasticpipetheirconnectionshouldadoptspecbond.
2.3.3硬塑料排水管道的伸缩节的设置应符合下列要求:
2.3.3Thedistributionoftheextensionjointsofthehardplasticdrainpipeshouldcomplywithfollowing:
i层高H≤4m,立管每层设一伸缩节;
层高H>
4m应根据设计伸缩量决定.
ioneextensionjointshouldbesetforverticalpipeineachlayerifthelayerH≤4m,thequantityoftheextensionjointshouldbedecidedbythedesignextensionlength.IfthelayerH>
4m.
ii当横支管至立管距离L>
2m时,应设伸缩节,但伸缩节之间的最大间距L≤4m.
iiWhenhorizontalpipefromtheverticalpipelengthL>
2m,extensionjointsshouldbeset,butthedistancebetweentheextensionjointsLshouldlessthan4m;
iii伸缩节承口应逆水流方向.
iiisocketchannelshouldberefluenttothedraindirection;
iv当立管穿越楼层处固定支承时,伸缩节不得固定,若伸缩节固定支承时,立管穿越楼层处不得固定
ivWhentheverticalpipeperforatesthefloorslabonlyoneoftheverticalandextensionjointcan
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 提取 车间 室内 排水 设计 说明