FGI351燃烧管理器安装操作手册Word格式.docx
- 文档编号:18234973
- 上传时间:2022-12-14
- 格式:DOCX
- 页数:45
- 大小:352.45KB
FGI351燃烧管理器安装操作手册Word格式.docx
《FGI351燃烧管理器安装操作手册Word格式.docx》由会员分享,可在线阅读,更多相关《FGI351燃烧管理器安装操作手册Word格式.docx(45页珍藏版)》请在冰豆网上搜索。
WARNING:
-EXPLOSIONHAZARD-
DONOTREMOVEORREPLACETHEPOWERTERMINALORFUSEUNLESSPOWERHASBEEN
SWITCHEDOFFORTHEAREAHASISKNOWNTOBENON-HAZARDOUS.
WARNING:
DONOTDISCONNECTEQUIPMENTUNLESSPOWERHASBEENSWITCHEDOFFORTHEAREAISKNOWNTOBENON-HAZARDOUS
DONOTSERVICEEQUIPMENTUNLESSPOWERHASBEENSWITCHEDOFFORTHEAREAISKNOWNTOBENON-HAZARDOUS
TableofContents
1ProductDescription1
1.1AboutThisManual1
1.2AbouttheFGI351&
IGN502
1.3SystemHardwareDescription3
1.4FGI351MainBoard3
1.5FGI351TerminalBoard4
1.6Configuration4
2Installation6
2.1SiteSelection6
2.2MountingtheFGI351Controller6
2.3MountingtheIGN507
2.4MountingtheSparker/FlameRod8
3WiringandJumperSettings9
3.1FromFGI351toIGN5012
3.2P&
ID’s15
4Set-UpandOperation25
4.1FrontPanel25
4.2Power-Up25
4.3FiringSequence26
4.4SettingThermocoupleHighTemp.Set-point28
4.5SystemErrorsandSafetyAlarms28
4.6Communications29
4.7Function3(ReadRegisters)30
4.8Function6and16(WriteRegisters)32
5TroubleShooting35
5.1InformationScreens35
5.2NormalOperation35
5.3Errors37
5.4OtherMessages42
6Appendix.................................................................................................................................A
©
2006TitanLogixCorp.
Rev.1,July2006
ii
1ProductDescription
1.1AboutThisManual
ThisinstructionmanualprovidesinformationspecifictotheTitanLogixCorp.FGI351BurnerManagementSystem.Otherperipheralequipmentshouldbesuppliedwithitsowninstructionmanualandthatmanualshouldbereferredtoforproperoperationoftheperipheralequipment.
ItisessentialthatthismanualbereadandunderstoodforproperinstallationandoperationofyournewFGI351.
Thismanualincludes:
INTRODUCTIONBrieflydescribesthekeyfeaturesandcomponentsoftheFG1
351andtheIGN50.
INSTALLATIONDetaileddescriptionofmountingandwiringofexternal
equipment.
OPERATIONDescribestheoperationanduseofthefeaturesoftheFGI351.
WIRINGDescribeshowtoconnecttheFGI351tothepowersupply,safetyswitches,communicationsystems,andoutputdevices.
TROUBLESHOOTINGDescribesseveralquickproblemsolvingtechniques.
SPECIFICATIONSDescribesthephysicalandoperationalcharacteristics.
Onlyqualifiedpersonnelshouldinstallthisproduct.Pleasereadthismanualbeforeinstallingthisproductandfollowallapplicablesafetyandelectricalregulationsasrequired.IfthisproductistobeinstalledinaClassI,Div.2area,followallextraregulationsrequiredforinstallingproductsinHazardouslocations.
Disclaimer
Theinformationinthisdocumentissubjecttochangewithoutnotice.TitanLogixCorpmakesnorepresentationsorwarrantieswithrespecttothecontentshereof.
IGN50
BurnerManagementTitanLogixCorp.hasdesignedtheFGI351/IGN50Burner
ManagementSystem(BMS)tomeettherequirementsofregulatoryauthoritiesandindustrytocontrolandmonitoratmosphericburnerappliancesupto10000000Btu/H.
ApplicationsThefollowingareexamplesofsuchappliances:
♦LineHeaters
♦Dehydrators
♦AmineandGlycolReboilers
♦SaltBathHeaters
♦Treaters
SystemKitThefollowingcomponentsareincludedinastandardFGI351systemkit:
♦FGI351Flame-Gard™/IgnitionBurnerManagementSystem
♦IGN50Sparker/FlameSenseModule
♦Ignitor&
FlameRodassemblywithignitioncable
♦Bracketformountingflamerod&
thermocoupletopilotassembly
♦TypeKthermocoupleencasedin446SSc/wshieldedthermocouplecable
♦SampleP&
ID’s
♦InstallationandOperationManual
FunctionOverviewTheFGI351/IGN50systemwillcontrolandmonitorthe
completeignitionandfiringsequence.Includingmonitoringforthepresenceofapilotflameandshutoffthegasflowiftheflamegoesout.Anautore-lightwilltrytore-ignitetheburneruptothreetimesifthereisaflamefailure.Therearededicatedalarminputsforlowfluidlevel,highbathtemperatureandlowandhighgaspressurethatcanbeconfiguredforhardorsoftlockouts.
DisplayAVacuumFluorescentDisplay(VFD)inthefrontdoorprovidesaneasytouseyetpowerfuluserinterface.Itprovidestheoperatorwithimportantinformationaboutburnerstatusandcertainoperationalvariables.
AnRS232/RS485MODBUScommunicationinterfaceisprovidedsothatahostcomputer,PLCorRTUcancontrolormonitortheFGI351/IGN50systems.
TheFGI351/IGN50cancontroltwomain,onepilot,andonehighfirestartvalve.AProofofClosureinputisprovidedfortheMainvalve.
SelfDiagnosticsSystemhardware,Ionizationinput,FlameMonitorinput,Proofof
Closure,andLowFireinputsareallmonitoredforcorrectperformancethroughoutalloperationsoftheFGI351.The
outputsarefedbacktotheCPUsoitcanensuretheoutputsareinthedesiredstateatalltimes.Forexample,beforetryingtoignitethepilottheCPUensuresallthevalveoutputsareoffandtheIonizationinputindicatesthataflameisn’tpresentatthepilot.Ifeitherofthesesituationsistrue,thedisplaywillindicatethenatureoftheproblemorindicatetheappropriateerrorcode.
1.3SystemHardwareDescription
ThreecircuitboardsaremountedintheFGI351controller:
theterminalboard,theI/Oboard,andthemainboard.Thefunctionofeachisdescribedinthesectionsthatfollow.
Fuses
F4=PilotF5=Main#1
F6=Main#2F7=HighFire
Figure1
FGI351CircuitBoards
1.4FGI351MainBoard
MainBoardSectionsThemainboardislocatedonthebacksideofthefrontdoorand
containstheCPUthatcontrolsalltheinputsandoutputs.Thedisplayindicatesthestatusoftheburnerandcertainoperationalvariables.MoredetailedinformationisprovidedintheFRONTPANELsectioninthismanual.Therearefivestatusindicatinglightemittingdiodesonthisboardtoindicatethefollowing:
LEDIndicatorsLEDIndicatorStatus
RunFlashestoindicatetheCPUisrunning.
IonizationDetectFlashestoindicatetheIGN50has
sensedthepresenceofaflameviatheIGN50.
PowerFailDetectLitwhenthepowersupplyvoltagedrops
below90%oftheratedvoltage,the351willshutdowntheburner.
TxFlasheswhentheCPUhasrecognizedamessagesenttoitfromthehostcomputerandisrespondingtoit.
RxFlasheswhenamessageisbeingreceivedfromthehostcomputer.
Figure2
FGI351MainBoard
1.5FGI351TerminalBoard
AllfieldwiringfortheFGI351unitisconnectedtotheterminalboardthroughconduitopeningsthefieldinstallermustcutinthebottomoftheFGI351enclosure.Allfusesarelocatedontheterminalboard.
EEPROMIfthemainboardortheI/Oboardaredamagedorreplaced,theconfigurationdatastoredontheterminalboardwillbemaintainedintheEEPROM.
1.6Configuration
TheFGI351hasafactoryconfiguredPre-Purgetimethatmustberequestedwhenorderingtheproduct.Howeverallotherconfigurationsettingscanbeeitherfactorysetorfieldsetbyapprovedpersonnel(seeAPPLICATIONDATAsheetatbackofmanual).Othersettingsinclude:
StartonPowerupRemoteStartEnableSoftStart
LowFireStartSleepEnable
SafetyAlarmLockouts
GeneralSafetyHighTemperatureLowLevel
HighGasPressure
LowGasPressure
Star