Takingthreetypicalhydrophobicoccasionsofdomestic600MWunitinapowerplantasanexampleforanalysisandcalculationofconcrete.
2.0采用疏水阀疏水时泄漏蒸汽损失的计算
2thedrainagesteamleakagelosscalculation
2.1中压疏水场合:
2.1mediumhydrophobicoccasions:
小机备用供汽管道疏水,温度为352.7℃,压力为4.675mpa。
Smallmachinesparesteampipedrainage,temperatureis352.7℃,thepressureis4.675mpa.
当疏水阀疏水后期排放蒸汽时的流量为:
Whenthedrainagedischargesteamdischargeforlate:
fs=cv/k×
0.139×
[(p1-p2)×
(p1+p2)]^0.5=5.4t/h
Fs=cv/k*0.139*((P1-P2)*(p1+p2))^0.5=5.4t/h
p1:
蒸汽压力(kpaa)
P1:
steampressure(kpaa)
p2:
背压(kpaa)
P2:
backpressure(kpaa)
fs:
蒸汽流量(kg/h)
FS:
steamflow(kg/h)
cv:
:
cv值,dn25的疏水阀以9计
Cv:
:
thevalueofCV,DN25inthe9metertrap
k:
1+0.0013(过热度)
K:
1+0.0013(superheat)
以每天平均流失蒸汽10分钟计算,1年损耗的蒸汽量总共为:
Steamfor10minutesperdayaverageloss,theamountofsteamlossin1years:
5.4t/h×
10/60h×
365=328.5吨
5.4t/h*10/60h*365=328.5tons
生产该参数的蒸汽所需要的热量:
Theparametersoftheproductionofsteamtoheat:
q=(hs-hw)=3082kj/kg-87kj/kg=2995kj/kg
Q=(hs-hw)=3082kj/kg-87kj/kg=2995kj/kg
hs:
过热蒸汽比焓
HS:
superheatedsteamenthalpy
hw:
常温下水的比焓
HW:
normaltemperaturewaterenthalpy
煤的低位发热量为17693kj/kg,不考虑锅炉效率,一年的损失折合消耗标准煤:
Lowcalorificvalueofcoalis17693kj/kg,notconsideringtheefficiencyoftheboiler,thelossoftheyearreducedconsumptionofstandardcoal:
2995kj/kg×
328.5t/17693kj/kg=56吨
328.5t/17693kj/kg=56tons
煤价若按350元/吨计,一年至少需消耗标准煤1.95万元。
Coalpricesby350yuan/ton,ayearofstandardcoalconsumptionofatleast19500yuan.
如果将锅炉效率考虑进去,实际损失要远高于上述的计算。
Iftheboilerefficiencyintoaccount,theactuallossisfarhigherthantheabovecalculation.
2.2低压疏水场合
2.2lowpressuresteam.
辅汽母管疏水温度为350℃,压力为1.6mpa。
Auxiliarysteamheadersteamtemperatureis350℃,thepressureis1.6mpa.
按上述方法计算得出:
Accordingtotheabovemethodtocalculate:
1年损耗的蒸汽量总共为:
110吨
Steamfor1yearsforatotallossof:
110tons
折合消耗标准煤:
19吨
Equivalentto19tonsofstandardcoalconsumption:
经济损失:
0.7万元
Economiclosses:
7000yuan
2.3高压疏水场合
2.3highpressuresteam.
轴封主汽汽源管道疏水,温度为546℃,压力为17.5mpa。
Themainshaftsealsteamsourcepipedrainage,temperatureis546℃,thepressureis17.5mpa.
1095吨
1095tons
205吨
Equivalentto205tonsofstandardcoalconsumption:
经济损失:
7.2万元
72000yuan
3.0采用自动疏水器疏水
3automaticsteamtrapsteam
自动疏水器在排放凝结水的过程中不会泄漏蒸汽,因此不会发生上述损失。
Thesteamdoesnotleakprocessofautomaticsteamtrapcondensateinemissions,sothelossdoesnotoccur.
根据有关统计资料均证明:
采用疏水器疏水有显著的节能降耗效果,因膨润土防水毯采用疏水器带来的经济效益,一般可在半年左右实现疏水器投资费用的回收,是一项简单易行、效果显著、投资回报快的革新挖潜技术改造项目。
Accordingtorelevantstatisticsshowthat:
theuseoftraphydrophobichassignificantenergysavingeffect,duetothetrapoftheeconomicbenefitsofrecyclingingeneral,canrealizethetrapinvestmentcostsinhalfayear,isasimple,effective,quickreturnofinvestmentprojectsoftechnologicaltransformationofnewpotentialleather.
在国内可以比较国产机组和进口机组疏水器应用的不同情况,一般国产机组上很难找到疏水器,而在进口机组上却很难数清究竟有多少疏水器,一般日本机组疏水器用量最大,两台350mw三菱机组有数百只之多,欧美机组约为日本机组的50%,且随着人们节能环保意识的增强在逐渐增加疏水器的应用部位及数量,例如各段抽汽、吹灰系统和各联箱、凝结水箱、扩容蒸发器以及压缩空气系统等等。
Candifferentcomparisonofdomesticunitsandimportsettrapusedinthedomesticunits,generallyitisdifficulttofindtraps,andintheimportedunitbutitisdifficulttokeepcountofhowmanytraps,mostgeneralJapanesesettrapdosage,two350MWMitsubishimachinegrouphashundredsofonly,andsetaboutastheJapaneseunit50%,andwiththeenhancementofpeople'
sawarenessofenergysavingandenvironmentalprotectioninagradualincreaseintheapplicationsitetrapandquantity,suchasextractionsteam,sootblowingsystemandeachheader,condensatetank,evaporatorandcompressedairsystemetc..
4.0其他因素造成蒸汽泄漏的分析计算
4otherfactorsanalysisandcalculationofleakageofsteam.
4.1汽水两相流冲蚀造成的阀门泄漏
4.1steam-watertwo-phaseflowerosioncausedbyvalveleakage
两相流对阀门和管道的冲刷是相当严重的。
疏水阀疏水过程中两相流的冲刷引起阀门的泄漏可按下面公式计算:
Two-phaseflowofvalveandpipingerosionisveryserious.Two-phaseflowdrainageprocessoferosioncausedbyvalveleakagecanbeaccordingtothefollowingformula:
fs=c×
(do/4.654)^2/k×
0.121×
p1
Fs=c*(do/4.654)^2/kx0.121xP1
c:
流量系数
C:
theflowcoefficient
do:
泄漏孔径(mm)
Do:
leakageaperture(mm)
1+0.0013(蒸汽过热度)
1+0.0013(steamsuperheat)
4.2维修成本方面的比较
Comparisonof4.2repaircosts
疏水阀通常需要通过解体阀门并根据泄漏程度对阀座研磨或更换阀塞、盘根等,这项工作每隔1~2年需定期进行,由于阀门数量多维护量也较大,在当前电厂“减员增效”趋势的要求下就显得很被动。
特别是电、气动执行机构的故障和检修,更增加了现场的水性油墨维护和检修工作的总量。
Thedrainvalveisusuallyrequiredbythedisintegrationofvalveaccordingtothedegreeofleakageofthevalveseatgrindingorreplacementofthevalveplug,packing,thisworkevery1to2yearsshouldberegular,becausealargenumberofmultidimensionalsupportamountofvalve,inthecurrentpowerplant"
synergismofdepletionofnumbers"
trendofdemandisverypassive.Especiallyforelectric,pneumaticactuatorfaultandmaintenancemechanism,increasetheamountofmaintenanceandrepairworkonthespot.
自动疏水器是一种完全自立式的特种阀门,其最大特点是没有任何人机接口,无需现场的任何整定和调试,也不需任何的操作(若采用一、二代传统疏水器,因内部有复杂的“杠杆-铰链”系统且为运动部件容易出现磨损、变形需要一定的维护和检修)。
据统计杠杆系统的故障率要占疏水器全部故障的90%以上,因此人们多采用第三代自由浮球式疏水器,由于它没有杠杆系统,整体故障率减少90%以上,基本没有什么检修工作量。
Automaticsteamtrapisakindofspecialvalvefullyself-supporting,itsbiggestcharacteristicisnoman-machineinterface,livewithoutanytuninganddebugging,butalsowithoutanyoperation(ifyouusetheoneortwogenerationoftraditionaltrap,becauseofthecomplex"
lever-hinge"
systemandmovingpartspronewear,deformationneedsomemaintenanceandrepair).Accordingtotheabovefaultstatisticsleversystemratetoaccountforallthe90%faulttrap,somanypeopleusethethirdgenerationoffreefloatingballtypesteamtrap,becauseitdoesnothavealeversystem,theoverallfailurerateislessthan90%,thebasicnomaintenanceworkload.
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 疏水 场合 蒸汽 损失 计算