英文文献.docx
- 文档编号:11554961
- 上传时间:2023-03-19
- 格式:DOCX
- 页数:9
- 大小:161.62KB
英文文献.docx
《英文文献.docx》由会员分享,可在线阅读,更多相关《英文文献.docx(9页珍藏版)》请在冰豆网上搜索。
英文文献
英文原文
Theoreticalanalysisoflow-temperaturehotsourcedriventwo-stageLiBr/H20absorptionrefrigerationsystem
W.B.Ma
GuangzhouInstituteofEnergyConversion,ChineseAcademyofSciences,
81CentralMartyrs'Road,Guangzhou,China
S.M.Deng
DepartmentofBuildingServicesEngineering,TheHongKongPolytechnicUniversity,HungHom,Kowloon,HongKong
Received19December1994;revised6June1995
Abstract:
Adetailedtheoreticalanalysisispresentedforatwo-stageLiBr/H20absorptionrefrigerationsystem,whichconsistsofanevaporator,alow-pressureabsorber,alow-pressuregenerator,ahigh-pressureabsorber,ahigh-pressuregenerator,acondenser,alow-pressureheatexchangerandahigh-pressureheatexchanger,drivenbyalow-temperaturehotsource.Acomparisonofresultsfromthetheoreticalanalysisandpreliminaryexperimentindicatesthatthetheoreticalanalysisdevelopedcanrepresentarealsystemwithareasonableaccuracy,andisusefulforfuturedevelopment.
Keywords:
absorption;water-lithium;bromide;two-stage
Literatureonabsorptionrefrigerationsystemsdrivenbyalow-gradeenergysourcesuchassolarenergyorwasteheatinindustrieshasbeenpresented1-5.Thesesystemscaningeneralbeclassifiedintotwotypesaccordingtothedifferentworkingfluids:
absorptionrefrigerationsystems,usingwater-lithiumbromide(LiBr/H20),water-ammonia(H20/NH3),water-lithiumchloride(LiCI/H20);andadsorptionsystems,usingammoniacalciumchloride(CaCI2/NH3),water-silica-gel,waterzealot,activatedcharcoal-methanol(CH3OH).However,onlyabsorptionrefrigerationsystemsusingwaterlithiumbromideasworkingfluidhavebeenoperatedsuccessfullyandhavefoundcommercialapplications.
Asingle-stageLiBr/H20absorptionrefrigerationsystemgenerallyconsistsofanevaporator,absorber,generator,condenserandsolutionheatexchanger.Thissystemoperateswithwaterasrefrigerantandlithiumbromideasabsorbent,andtheheatsourcerequiredtorunsuchasystemshouldhaveatleastatemperatureofover86°CinordertoachieveareasonableCOP6.However,thereexistsalargeamountoflow-temperatureheatsourceoflessthan86°C,suchaswasteheatinindustries,solarenergyandgeologicalheat.Iftheselowtemperatureheatsourcescanbeusedorreused,itwillnotonlyimprovetheoverallsystemenergyefficiency,butdecreasetheheatpollutiontotheenvironmentaswell.
Atwo-stageLiBr/H20absorptionrefrigerationsystem,withwaterasrefrigerantandlithiumbromideasabsorbent,canhoweverbeoperatedwithalowertemperatureheatsourcefrom75to86°C,andacoefficientofperformance(COP)ofabove0.38forsuchasystemcanbeachievedwhenthecondensercoolingwatertemperatureis32°Candthechilledwatersupplytemperatureis9°C,notablywhentheoutlettemperatureoftheheatsourceislowerthan64°C7.Thereforeatwo-stageLiBr/H20absorptionrefrigerationsystemisusefulandsignificantinrecoveringlowtemperaturewasteheatinindustries,andinapplyingsolarenergyandgeologicalheat.Researchworkforsimulatingsingle-stageabsorptionrefrigerationsystems,double-effectabsorptionrefrigerationsystemsandabsorptionheatpumpshasbeenreportedbyanumberofresearchers,includingBogart8,Vilestetal9,andGrossmanetal1°-12,butlittleresearchfortwo-stageLiBr/H20absorptionrefrigerationsystemshasbeenpresented.Thispaperdescribesthetheoreticalanalysisfortheperformanceofatwo-stageabsorptionrefrigerationsystemunderdifferentoperatingconditions,andacomparisonbetweenthetheoreticalanalysisandpreliminaryexperimentalresultsispresented
.
Assumptions
Thefollowingassumptionsweremadeinthecourseofanalysis.
1.ThetemperatureandconcentrationofLiBraqueousareinequilibriumatthesaturatedpressureofLiBraqueous.
2.Heatlosstooutsidethesystemisneglected.
3.TheLiBrfractionpressureisneglected:
i.e.thepressureinthevaporphaseisequaltothesaturatedpressureofwater.
Systemdescription
Thetwo-stageLiBr/H20absorptionrefrigerationsystemshownschematicallyinFigure1consistsofanevaporator,low-pressure(LP)absorber,LPgenerator,LPsolutionheatexchanger,high-pressure(HP)absorber,HPgenerator,HPsolutionheatexchanger,condenserandtwosolutionpumps.ThepressureintheevaporatorisequaltothatintheLPabsorber,Pe.ThepressuresintheLPgeneratorandtheHPabsorberareequal(Pm)asarethepressuresintheHPgeneratorandthecondenser(Pc).TheorderofthesepressuresisPe Therefrigerantwateriscirculatedthroughtheevaporator,LPabsorber,LPgenerator,HPabsorber,HPgeneratorandcondenser.Afterwatervaporhascondensedinthecondenser,itreturnstotheevaporatorthroughanexpansionvalve.However,theabsorbentLiBraqueoussolutioniscirculatedwithintwoseparatecycles: alow-pressurecyclebetweentheLPabsorberandtheLPgenerator,andahigh-pressurecyclebetweentheHPabsorberandtheHPgenerator. Figure2showsthetwo-stageLiBr/H20absorptionrefrigerationcycleonalogP-Tdiagram.Thecycleindicatedby21-71--51--41--81--91--21isthelow-pressurestage,andthatby2h--7h--5h--4h--8h--9h--2histhehighpressurestage,correspondingtopointsinFigure1.Ascomparedwithasingle-stageabsorptionrefrigerationsystem,therearetwoadditionalcomponents,istheHPabsorberandLPgenerator,inatwo-stagesystem.TheseareusedtoconcentratetheLiBraqueoussolutionintheLPstagecyclesothatitispossibletoproduce7-9°Cchilledwaterintheevaporator. Theoreticalanalysisoftheabsorptioncycle Low-pressurecycle WatervaporizedintheevaporatorisabsorbedbytheconcentratedsolutionofLiBrfromtheLPgeneratorthroughtheLPsolutionheatexchanger;thentheLiBraqueoussolutionchangestotheweaksolution.Theoutlettemperatureandconcentration(T12andXl,)oftheLiBrsolutionaredeterminedbasedonthepressurePeandtemperatureTwiofthecoolingwater: TheweaksolutionisthenpumpedtotheLPgeneratorthroughtheLPsolutionheatexchanger,inwhichitexchangesheatwiththeconcentratedsolutionfromtheLPgenerator.IntheLPgenerator,weaksolutionisheatedtoT~4andconcentratedtostrongsolutionXlr.T14andX'lrareinequilibriumatpressurePm: ThenstrongsolutionreturnstotheLPabsorbertoformthelow-pressurecycle. High-pressurecycle ThestrongsolutionXhrintheHPabsorberfromtheHPgeneratorthroughtheHPsolutionheatexchangerabsorbsvaporgeneratedintheLPgenerator.Theweaksolution)(haisthenpumpedtotheHPgeneratorthroughtheHPsolutionheatexchanger.Similarly,Xh,andTh2aredeterminedbythetemperatureTwiofthecoolingwaterandPro: TheweaksolutionintheHPgeneratorisheatedtoTh4bytheheatsourceandconcentratedtostrongsolutionXhr.Th4andXhrareinequilibriumatpressurePc: ThestrongsolutionconcentratedintheHPgeneratorthenreturnstotheHPabsorber,formingthehighpressurecycle. Massandenergybalance Evaporator: LPabsorber: LPgenerator: LPheatexchanger: (19) HPabsorber: HPgenerator: HPsolutionexchanger: (26) Condenser: Totalinputheat: Totaloutputheat: Totalenergybalance: Coefficientofperformance(COP): Statevariables,temperatures,concentrationsandenthalpiesofLiBraqueoussolutionatpoints1-9werecalculatedbyliterature13-19. Thetemperaturedifferences(ΔT)betweentwofluidsattheexitsoftheheatexchangersinthesystemweredeterminedbasedontheoperatingparametersandheatexchangerstructureindifferentheatexchangers.Forexample,intheevaporator,thetemperaturedifferencesbetweenthechilledwaterandrefrigerantattheentranceandexitare7and2°Crespectively. Results Analysisresultswereobtainedusinglow-temperaturehotwaterasheatsourceandarediscussedbelow: Effectofhotwatertemperature Figure3showstheeffectofthetemperatureofthehotwateronthecoefficientofperformance(COP).Itisclearthatthetwo-stageLiBrabsorptionrefrigerationcannotbeoperatediftheoutlettemperatureoftheLiBraqueoussolution,Th4orTl4,intheHPgeneratorandLPgeneratorisbelow58°C,undertheconditionwhenthetemperatureofchilledwateris7°candthatofthecondensercoolingwateris32°c.IfthetemperaturedifferencebetweentheinlettemperatureofthehotwaterandtheoutlettemperatureoftheLiBraqueoussolution,Th4orT14,intheHPgeneratorandLPgeneratorisassumedtobe15°C,thenatwo-stageLiBr/H20absorptionrefrigerationsystemcannotbeoperatedwhenthetemperatureofthehotwaterThi,isunder73°C.TheCOPofatwo-stageLiBr/H20absorptionrefrigerationsystemincreaseswiththetemperatureofthehotwater,butwhenthetemperatureThi,isabove87°C,orTh4andT14areabove72°C,theincreaseofCOPisverysmall.Becausetheheatlossincreaseswhenthetemperatureoftheheatsource,Thi,isincreased,thetemperatureoftheheatsourceThiabove87°Cisnotadvantageousforatwo-stageLiBr/H20absorptionrefrigerationsystem.Figure3showsthatthebesttemperaturerangeoftheheatsourceisbetween75°Cand87°Cforatwo-stageLiBr/H20absorptionrefrigerationsystem. Effectofchilledwatertemperature,Tcho TheinfluenceofdifferentchilledwatertemperatureTchoontheCOPofatwo-stageLiBr/H20absorptionrefrigerationsystemisshowninFigure4.Atwo-stageLiBr/H20absorptionrefrigerationsystemismoresuitableforsupplyingchilledwaterofover9°Cforairconditioningorotherapplications.Ifthetemperatureofthechilledwaterisunder7°C,theCOPisverysmallwhenthetemperat